background image

2  

Status Screen

5

Figure 2-1

SMART TOUCH Status Screen

To monitor and record the operation of the heater, click on
the 

Status

tab along the top of the Main Screen window

(FIG. 1-1, page 4).  When using the SITECS937Lab program,
you will need to choose which controller you wish to monitor.
The Status Screen will appear (see FIG. 2-1 above).  The
screen is divided into several sections.  

The Sensors section displays the current temperatures seen by
the Inlet, Outlet, System Inlet, System Outlet, Tank, Outdoor,
and Flue sensors.  It also shows the delta T across the heat
exchanger and the voltage being applied to the 0-10Vdc input
(FIG. 2-1).  The controlling sensor is shown below the items
mentioned above.  The default controlling sensor is the Outlet
sensor.  If a System Supply sensor is connected, the control
will automatically use it as the controlling sensor.

Below the temperature readings are Derivative Flue and
Derivative Outlet.  These show how quickly these
temperatures are changing.  The control will take certain
actions based on these values.  For instance, if the outlet
temperature rises too quickly, the control will force the heater
to run at low fire.  Finally, the 0-10Vdc input Voltage and
Flame Current are shown.

To the right of the sensor temperature readings are the various
setpoints.  The SH setpoint is the setpoint the SMART TOUCH
uses during a space heating call for heat.  Note that this setpoint
will depend upon the outdoor temperature if the outdoor air
sensor is connected.  When the 0-10Vdc input is used, this
setpoint will vary with the input voltage if it is used to control
the setpoint.  The HW setpoint is the setpoint used when a Tank
sensor is connected.  The HW Mod Setpt is the outlet
temperature setpoint used when heating an indirect HW tank.
The dSP setpoint is not used.  Below these is a check box
indicating if Night Setback is active or not.  

Below the Sensors section is the Inputs section (FIG. 2-1).  This
section displays the status of the Enable (SH Thermostat)
Input, HW Thermostat, Manual Reset High Limit, Flow
Switch/Low Water Cutoff (optional), Gas Pressure Switch,
Louver Proving Switch (optional), Air Pressure Switch, Blocked
Drain Switch, Auto Reset High Limit Switch, and the status of
the SH and DHW demands from ModBus.   

Next to the Inputs section is the Outputs section (FIG. 2-1).
This section shows the status of the Boiler (secondary) pump,
System (primary) Pump,  HW Pump, Blower, Gas Valve,
Run-time Contacts, and Alarm Contacts.

PC Program Instructions

Summary of Contents for SMART TOUCH

Page 1: ...SYNC Installation and Operation Manual and the SYNC Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial pro...

Page 2: ...3 PC to Unit Connection 3 Starting the Program 4 6 2 Status Screen 5 6 3 Graphics Screen 7 4 Fault History Screen 8 5 Cascade Screen 9 6 PARAMETERS Parameter Information Screens 10 Changeable Paramet...

Page 3: ...r assigned to the USB cable above The programs display temperatures in F If you wish to display temperatures in C click on the Settings tab along the top of the Main Screen window and move the cursor...

Page 4: ...the upper left hand corner of the window A window opens in which you can type in the password see FIG 1 3 Note that the password is case sensitive and is in all CAPS Click on the Ok button or press th...

Page 5: ...o run at low fire Finally the 0 10Vdc input Voltage and Flame Current are shown To the right of the sensor temperature readings are the various setpoints The SH setpoint is the setpoint the SMART TOUC...

Page 6: ...active limits if any the last active limit the burner status the last fault and the date and time as stored in the SMART TOUCH PC Program Instructions While in the SMART TOUCH Status Screen you can g...

Page 7: ...he desired scale The top number represents F and the bottom number represents C Press the Ok button to close the Options window The background color of the Graphics Screen can be changed by pressing t...

Page 8: ...is shown as well as the number of successful and failed ignition attempts Finally a count of internal checks is shown The total number of occurrences of certain faults are also stored in the control a...

Page 9: ...t is a check box indicating if the temperature regulation is being held constant and if the Ramp Delay feature is active The Freeze P1 regulation box is checked when the next controller can be started...

Page 10: ...an adjustment to a parameter select the parameter to be changed from the appropriate set Click on the box next to the parameter and type in the value for the parameter Once an adjustment has been mad...

Page 11: ...stable The time range for each ramp delay is adjustable from 1 minute to 40 minutes with the total of all 6 ramp delays not to exceed 109 minutes The default delay time for Periods 1 2 and 3 is 2 minu...

Page 12: ...switching boiler on Parameter 2DJ is the minimum time delay between starting one burner and starting the next burner in the Cascade The range for this parameter is 0 seconds to 255 seconds The default...

Page 13: ...mperature setpoint for fixed operation or the maximum temperature setpoint when the outdoor air sensor is used This parameter can be changed by accessing parameter 4AA The temperature range of this pa...

Page 14: ...alue is 0 This feature will be active if this parameter is set to anything other than 0 Night setback temperature NSB Setp Once the internal clock has been set correctly the night setback feature can...

Page 15: ...has occurred or the maximum user setpoint has been reached Once the SH demand has been satisfied the setpoint will revert back to its calculated setting The boost temperature can be changed by accessi...

Page 16: ...ndow click on the tab labeled 4D Pump Delay to set the delay time for the boiler system and HW pumps see FIG 6 8 below Figure 6 8 Parameter Set 4D SH pump delay after SH demand Boiler Pump D This feat...

Page 17: ...re rises to or above this point the water temperature will be at its minimum setpoint This parameter can be changed by accessing parameter 4FD The temperature range of this parameter is 30 F 34 C to 9...

Page 18: ...eter 4GD The voltage range for this parameter is 0Vdc to 4GC The default value is 10Vdc Min BMS voltage to start demand BMS V Heat If parameter 4GK is set to 1 then the heat demand will be generated b...

Page 19: ...pear confirming that the file was saved Note that the new file name appears in the lower right hand corner of the SMART TOUCH PC program window BMS Voltage at min power BMS V min mod If parameter 4CB...

Page 20: ...Revision Notes Revision A initial release SYNC PCP Rev A Printed in the USA 4 10...

Reviews: