background image

9

5  

Cascade Screen

Figure 5-1

Cascade Screen

The Cascade Screen provides the status of the cascade system.
The PC must be connected to the Leader (address 0-1)
appliance.  Click on the 

Cascade

button along the top of the

Main Screen window (FIG. 1-1).

The Cascade System area shows the power demand and
setpoint, the boiler pump status, the boiler status, and the
priority of each controller in the cascade.  If a system supply
sensor  is connected to the Leader controller, the cascade
control will send a fixed setpoint of 185°F (85°C) and a power
(% modulation) command to all the heaters as required to
maintain the controlled temperature at the setpoint.  If a
system supply sensor is not connected (NOT recommended),
the Leader will send the space heating setpoint to all of the
boilers in the cascade and each controller will fire as required
to hold their outlet sensors to this setpoint.  

The Priority column indicates the order in which the
controllers will fire to meet the load.  This order changes every
hour during the first day of operation, and every 24 hours
thereafter.

The Sensors area displays the system supply temperature, and
space heating setpoint (see FIG. 5-1).

Beneath this area is a check box indicating if Night Setback is
active.  Beneath that is a check box indicating if the
temperature regulation is being held constant, and if the
Ramp Delay feature is active.  The Freeze P1 regulation box is 

checked when the next controller can be started up, but is held
off by one of the timers.

The Status area displays several important parameters.  The
Cascade Pump gives the status of the system pump output, and
the type of heat demand (Space Heating or HW).  The Cascade
power shows the power target for the cascade, and the total
power available.  This target power may not be the same as the
total power shown in the Cascade System area, due to the
various time delays described below.  The Cascade Max and
Cascade Min values show the maximum and minimum fan
speed percentages available in all of the heaters.  The Off Timer
and On Timer are used to force each controller to have a
minimum off and on time, to prevent short cycling.  The Block
Switch on timer is started whenever a controller is commanded
to start, and the next controller is prevented from starting until
this timer times out.  This allows time for the system supply
sensor to read the temperature change resulting from firing the
last controller, before starting the next.

By clicking on the 

Options

button, a log file can be defined, and

logging can be started and stopped in the same way as with the
Status and Graphics Screens previously described.  A bitmap of
the current screen can also be saved if desired.

PC Program Instructions

Summary of Contents for SMART TOUCH

Page 1: ...SYNC Installation and Operation Manual and the SYNC Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial pro...

Page 2: ...3 PC to Unit Connection 3 Starting the Program 4 6 2 Status Screen 5 6 3 Graphics Screen 7 4 Fault History Screen 8 5 Cascade Screen 9 6 PARAMETERS Parameter Information Screens 10 Changeable Paramet...

Page 3: ...r assigned to the USB cable above The programs display temperatures in F If you wish to display temperatures in C click on the Settings tab along the top of the Main Screen window and move the cursor...

Page 4: ...the upper left hand corner of the window A window opens in which you can type in the password see FIG 1 3 Note that the password is case sensitive and is in all CAPS Click on the Ok button or press th...

Page 5: ...o run at low fire Finally the 0 10Vdc input Voltage and Flame Current are shown To the right of the sensor temperature readings are the various setpoints The SH setpoint is the setpoint the SMART TOUC...

Page 6: ...active limits if any the last active limit the burner status the last fault and the date and time as stored in the SMART TOUCH PC Program Instructions While in the SMART TOUCH Status Screen you can g...

Page 7: ...he desired scale The top number represents F and the bottom number represents C Press the Ok button to close the Options window The background color of the Graphics Screen can be changed by pressing t...

Page 8: ...is shown as well as the number of successful and failed ignition attempts Finally a count of internal checks is shown The total number of occurrences of certain faults are also stored in the control a...

Page 9: ...t is a check box indicating if the temperature regulation is being held constant and if the Ramp Delay feature is active The Freeze P1 regulation box is checked when the next controller can be started...

Page 10: ...an adjustment to a parameter select the parameter to be changed from the appropriate set Click on the box next to the parameter and type in the value for the parameter Once an adjustment has been mad...

Page 11: ...stable The time range for each ramp delay is adjustable from 1 minute to 40 minutes with the total of all 6 ramp delays not to exceed 109 minutes The default delay time for Periods 1 2 and 3 is 2 minu...

Page 12: ...switching boiler on Parameter 2DJ is the minimum time delay between starting one burner and starting the next burner in the Cascade The range for this parameter is 0 seconds to 255 seconds The default...

Page 13: ...mperature setpoint for fixed operation or the maximum temperature setpoint when the outdoor air sensor is used This parameter can be changed by accessing parameter 4AA The temperature range of this pa...

Page 14: ...alue is 0 This feature will be active if this parameter is set to anything other than 0 Night setback temperature NSB Setp Once the internal clock has been set correctly the night setback feature can...

Page 15: ...has occurred or the maximum user setpoint has been reached Once the SH demand has been satisfied the setpoint will revert back to its calculated setting The boost temperature can be changed by accessi...

Page 16: ...ndow click on the tab labeled 4D Pump Delay to set the delay time for the boiler system and HW pumps see FIG 6 8 below Figure 6 8 Parameter Set 4D SH pump delay after SH demand Boiler Pump D This feat...

Page 17: ...re rises to or above this point the water temperature will be at its minimum setpoint This parameter can be changed by accessing parameter 4FD The temperature range of this parameter is 30 F 34 C to 9...

Page 18: ...eter 4GD The voltage range for this parameter is 0Vdc to 4GC The default value is 10Vdc Min BMS voltage to start demand BMS V Heat If parameter 4GK is set to 1 then the heat demand will be generated b...

Page 19: ...pear confirming that the file was saved Note that the new file name appears in the lower right hand corner of the SMART TOUCH PC program window BMS Voltage at min power BMS V min mod If parameter 4CB...

Page 20: ...Revision Notes Revision A initial release SYNC PCP Rev A Printed in the USA 4 10...

Reviews: