background image

7

4  

Commissioning the solar system

General

■ 

Before commissioning,  all piping,  connections and saftey 

  equipment should be checked to ensure that they are 

 

 

 

    correctly installed.

■ 

All pre-fitted solar station screw connections are firmly 

   tightened in the factory so that they do not usually need 
    retightening.

■ 

Seal integrity must be tested when commissioning and a 

    pressure test must be completed.

■ 

Fill the complete solar system with Lochinvar/TiSUN solar 

   liquid only. The mixing ratio should be adapted to local 
    conditions.

■ 

Never flush or pressure test the complete solar system with 

    just water. Flushing the system with water only can cause a 
    freezing  hazard.

Filling, flushing and bleeding

■ 

There is one fill valve with hose connection for filling, 

    flushing and draining the solar system on both the safety 
     group and sensor measurement section.

■ 

Connect the pressure hose (forward flow) to the safety 

   group’s filling connection under the pressure gauge and 
     open fill/flush valve. 

■ 

Connect the flushing hose (return) to the flushing 

   connection on the sensor measuring section and open 
      fill/flush valve. 

■ 

Refer to “Technology, installation and commissioning: 

   Operation, multi-function ball valve and check valve” on 
     page 6.

■ 

Open the supply ball valve (by turning the red thermometer 

    handle counter-clockwise until it stops).

■ 

Close return ball valve (by turning the blue thermometer 

    handle clockwise, until it stops).

■ 

If necessary, the supply and return check valve can be 

  opened by moving the thermometer handles to the 45

°

 

    position.

■ 

Put sufficient solar liquid in the tank of a filling and flushing 

   pump (not supplied). The mixing ratio  should be adapted 
    to local conditions in terms of freeze protection.

■ 

Fill the solar system via the filling and flushing pump and 

   then flush the solar circuit for at least 15 min. to purge all of 
   the air out of the circuit.

■ 

Close the fill/flush valve (return) with the filling and 

      flushing pump running and increase the system pressure to 
  60 psi. The system pressure can be read at the 
     pressure gauge.

■ 

Close the fill/flush valve (forward flow) and switch off the 

    filling and flushing pump.

■ 

Open return ball valve (by turning the blue thermometer 

    handle 90

°

 counter-clockwise until it stops).

■ 

The solar system features an air separator. Open the bleeder 

    valve until the solar liquid exits free of air bubbles.

■ 

Only if collector bleeder is installed: Bleed the system on the 

    collector until the solar liquid exits free of bubbles.

■ 

If necessary, increase the test pressure again to 60 

   psi  and check the system for leaks. If the pressure gauge     
    shows the pressure dropping substantially, you have a leak   
    in the system.

■ 

Set the operating pressure to 60 psi as prescribed by the 

 system 

manufacturer 

■ 

Start up the circulation pump at maximum speed and allow 

    liquid to circulate for at least 15 min.

■ 

Remove the filling station hoses and screw the  caps on the 

    flushing and filling valves. 

■ 

Check the system again for leaks. Use the red and blue 

   thermometer handles to fully open the forward flow and 
    return ball valves. 

■ 

Activate speed control on solar control unit. The highest 

    speed level should be set on the pump (phase control).

Note

:

 The minimum speed set on the solar control unit must 

 

  not fall below the pump’s minimum nominal speed. 

 

   Note instructions for pump and solar control unit.

■ 

Once the installation settings have been completed and 

     checked, fit the solar station’s front insulation shell. 

■ 

Refer to the collector manufacturer’s recommendations for 

    minimum flow requirements.

 

SL-PS Installation & Operation Manual

Summary of Contents for TISUN PS1000

Page 1: ...only be used by a qualified heating installer service technician Read all instructions before installing Perform steps in the order given Failure to comply could result in severe personal injury death...

Page 2: ...to personal injury or property damage HAZARD DEFINITIONS 2 1 GENERAL INFORMATION Included components 3 4 2 INSTALLING THE SOLAR STATION Installing the solar station on a wall 5 Installing the relief v...

Page 3: ...operation The provisions stated in DIN EN 12976 1 should be observed when installing solar systems The expansion tank should be regularly checked according to DIN 4807 Solar systems should be grounde...

Page 4: ...with mounting kit Installation kit Wall and tank bracket with mounting kit 1 General Information Solar Control unit LCD Plus solar control unit with integrated energy balance function 2 collector and...

Page 5: ...ion should be noted The safety valve must be easily accessible No valves should be placed between relief valve and pump station The relief valve should be piped to a suitable drain as close as possibl...

Page 6: ...tion 40 Ft lb 1 1 4 screw connection 66 Ft lb 1 1 2 screw connection 96 Ft lb Operation multi function ball valve and check valve The forward flow ball valve must be open for filling flushing and blee...

Page 7: ...erms of freeze protection Fill the solar system via the filling and flushing pump and then flush the solar circuit for at least 15 min to purge all of the air out of the circuit Close the fill flush v...

Page 8: ...4 0 4 5 5 0 5 5 6 0 6 5 7 0 7 5 8 0 Volumetric flow rate GPM Residual delivery height Ft Max residual delivery height pressure drop of components Solar group with Grundfos UP 25 120U pump and GF Sens...

Page 9: ...Assignment of measurement range 32 212 F is equal to 0 5 3 5V Temperature rate calculation T 32 F U 0 5 V 3V 180 F Figure 6 4 VFS 2 40 temperature output signal VFS 2 40 output signal temperature Assi...

Page 10: ...size DN20 Measuringrange 26 3 17 GPM 5 10 5 GPM Measuring range 5 10 5 GPM Output signal Q 0 5 to 3 5 V proportional to GPM Output signal T 0 5 to 3 5 V proportional to 32 212 F Max pressure 145 psi...

Page 11: ...FLAT SEALS FOR PUMP Size 30 x 22 x 2 1 Size 44 5 x 33 x 2 1 1 2 Material AFM 34 light grey Long term temperature Liquid 482 F water vapor 360 F Peak temp briefly 720 F FLAT SEAL FOR SAFETY GROUP Size...

Page 12: ...0 UPS 25 99U 1 1 2 180 F12K09 115V 60Hz 13 Solar control unit LCD plus USA 115 Volt w SD card 14 SPS0250 Sensor direct 0 26 3 17 gpm w cable SPS0500 Sensor direct 0 50 10 5 gpm w cable 15 Power cord U...

Page 13: ...16 Solar cross piece cpl USA w reducing pc and cap 17 Flow sensor housing 0 50 10 5 gpm w fill flush valve USA 18 Safety group KS0150 USA 19 Solar control unit LCD plus USA 115 Volt w SD card 20 UP 2...

Page 14: ...x 33 Ft lb When tightening the clamp ring screw connection use two wrenches one wrench to prevent the pumping station from turning Disassembling the solar station Wall bracket for repairs and service...

Page 15: ...atures and system pressures Allow pump to cool first Fully unscrew bleed screw and check ease of movement of pump rotor by turning the slotted shaft end with a screwdriver use force to turn if necessa...

Page 16: ...Revision Notes Revision A ECO C06520 initial release Revision B ECO C07610 reflects formatting adjustments SL PS I O Rev B 3 11...

Reviews: