2
Product Description
Logano G334X – 6 720 811 237 (2014/05)
6
2.8
Dimensions and Specifications
2.8.1
Logano G334X dimensions
Fig. 2
Connections and dimensions for Logano G334X, dimensions in inches (dimensions in mm)
[1]
Boiler supply/Storage tank supply
[2]
Gas conn main shutoff valve
[3]
Return safety line/draining
[4]
Boiler return
1 ½ʺ
28
2
⁄
3
1
1
⁄
4
4
3
⁄
5
1 ½ʺ
¾ʺ
13
2
⁄
3
43
1
⁄
10
23
2
⁄
3
25
3
⁄
5
2
3
⁄
5
40
2
⁄
3
6 720 810 547-02.1T
3
4
2
1
Boiler size
Unit
73
92
116
132
Ignition heat load
MBTU/hr
301
378
476
541
kW
88.2
110.7
139.4
158.4
Nominal output
MBTU/hr
249
314
396
450
kW
73
92
116
131.8
Dimension A
inches
34.5
41.7
48.8
55.9
mm
876
1059
1240
1420
Dimension B
(VENT)
inches
8
9
10
10
mm
203
229
254
254
Minimum capacity of the safety relief valve
lb/hr
249
314
396
450
kg/h
113
142
180
204
Number of burner rods
Qty.
5
6
7
8
Water volume
US Gal.
9.2
11.4
13.5
15.6
l
34.8
43.2
51.1
59.1
Dry weight
lbs
758
930
1093
1265
kg
344
422
496
574
Table 4 Dimensions