background image

  
                                                                                                                                             - 12 -

 

 

6

 

 ACCESSORIES  

The product comes with a safety valve and a thermometer. Hinges and bolts are mounted onto the heater. It 
is in your own interest to check the completeness of the accessories. 

   With  regard  to  various  types  of  carrying  masonry  and  broad  assortment  of  special  anchorage  material 
available  at  the  market,  the  manufacturer 

does  not

 

provide

  heaters  with  this  material.  The  anchorage 

system has to be selected individually, depending on the conditions. We recommend an authorised company 
perform mounting on the wall and anchorage, or discuss the anchorage with a professional. 

7

 

 WALL MOUNTING 

Prior to mounting, check the loading capacity of the wall, If needed, reinforce it. Choose a suitable anchorage 
material to suspend the heater, depending on the type of the wall. The water heater shall only be mounted 
in vertical position so that the lower edge of the heater is placed at least 60 cm above the floor. 

8

 

 PLUMBING FIXTURE 

Connection  of  heaters  to  plumbing  fixtures  is  illustrated  on  Figure  6.  For  potential  disconnection  of  the 
heater, the service water inlets and outlets must be provided with screw coupling Js 3/4“. For operation, the 
heater must be equipped with a safety valve. The safety valve is mounted on the cold water inlet identified 
with a blue ring. 

 

 

Each hot service water pressure heater must have a safety valve with a membrane spring.   

The safety  valve must be easily  accessible, as  close  to  the  heater  as  possible. The  inlet pipes must have  at 
least the same clearance as the safety valve. The safety valve is placed high enough to secure dripping water 
drain by gravity. Safety valves with fixed pressure settings from the manufacturer are used for the assembly. 
The start-up pressure of the safety valve must correspond to the max. allowed pressure of the water heater. 
If  the  water  main  pressure  exceeds  such  value,  a  reduction  valve  must  be  added  to  the  system,  whose 
working pressure is to be set to 80% of the start-up pressure of the safety valve.

 

Necessary pressure can be 

found in table 2. No stop valves can be put between the heater and the safety valve. During assembly, follow 
the guide provided by the safety equipment manufacturer. It is necessary to check the safety valve each time 
before putting it into operation. It is checked by manual moving of the membrane from the seat, turning the 
make-and-break device button always in the direction of the arrow. After being turned, the button must click 
back into a notch. Proper function of the make-and-break device results in water draining through the safety 
valve outlet pipe. In common operation, such a check needs to be implemented at least once a month, and 
after  each  heater shutdown  for more than  5  days.  Water  may  be dripping  off the drain  pipe of the safety 
valve; the pipe must be open into the air, pointed down; environment temperatures must not drop below 
zero.  

 

 

Summary of Contents for LX ACDC/M+K 100 A

Page 1: ...DC M K 200 A B C LX ACDC M KW 200 A B C MANUFACTURER LOGITEX spol co s r o Ltd portovcov 884 4 SK 02001 P chov Phone no 421 42 4710200 Fax 421 42 4642300 logitex logitex sk Made in Dru stevn z vody Dr...

Page 2: ...C HOT WATER HEATER 10 4 4 DIMENSIONS OF LX ACDC M K 100 A B C LX ACDC M K 125 A B C LX ACDC M K 160 A B C LX ACDC M K 200 A B C 11 5 Operating activity 11 6 Accessories 12 7 Wall mounting 12 8 Plumbi...

Page 3: ...be observed The product s reliability and safety have been verified by tests implemented by EVP Nov Dubnica The manufacturer reserves the right for engineering modification of the product The product...

Page 4: ...ing qualities Voltage 30V 10 and Current 8 3A 5 1 FV panel Photovoltaic panels can be installed at any place with maximum sunshine and south oriented but must not be freely accessible due to the fact...

Page 5: ...ementary system for already existing system of water heating for users using a system in which the heater is placed before or after the system All water heaters of the M K W line are equipped with a t...

Page 6: ...m photovoltaic panels keeps heating the water to the preset temperature on thermostat T2 If the water temperature drops water withdrawal to below 45 C with the sun shining the water is very quickly an...

Page 7: ...n control light signalizes the input of the direct current from the photovoltaic panels If it is on the panels are producing electrical energy Heating water by means of AC current from network is indi...

Page 8: ...hrough its reaction with water it creates an environment that prolongs the lifetime of the tank The design of the anode and the material used comply with the standard EN 12438 A thermometer that trans...

Page 9: ...9 4 TECHNICAL DESCRIPTION 4 1 DIAGRAM OF LX ACDC M K 100 A B C LX ACDC M K 125 A B C LX ACDC M K 160 A B C LX ACDC M K 200 A B C Figure 2 4 2 DIAGRAM OF LX ACDC M KW 200 A B C Figure 3...

Page 10: ...10 4 3 DIMENSIONS OF THE LX ACDC M KW 200 A B C HOT WATER HEATER Figure 4...

Page 11: ...cet hot water valve is opened the water from the water supply conduit pressed out by cold water pressure flows out of the heater Hot water flows out through the top part and water flowing in remains i...

Page 12: ...afety valve with a membrane spring The safety valve must be easily accessible as close to the heater as possible The inlet pipes must have at least the same clearance as the safety valve The safety va...

Page 13: ...afety valve If the pressure in the water piping exceeds 0 6 MPa we recommend installation of a pressure control valve as well The appliance is not designed to be serviced by people including children...

Page 14: ...Connection to electric network shall be executed only after the plumbing has been installed Elements for disconnection from the electric grid must be built into the fixed electric grid distribution t...

Page 15: ...dicator of DC spiral activity TP Heat fuse S3 Indicator of AC spiral activity St1 Contactor for switching on FV heating St2 Contactor for switching between R1 AC Heating element R2 DC Heating element...

Page 16: ...ing system Check proper placement of operating and safety thermostat sensors The sensors in the well must be inserted all the way in first the operating and then the safety thermostat b Open the hot w...

Page 17: ...ting the LX ACDC M KW 200 A B C for floor heating systems for low energy and passive homes Figure 8 Fire fighting regulations for heater installation are defined in relevant standards The heater must...

Page 18: ...rial has been paid for the packaging in which the water heater was delivered The service fee was paid in accordance with Act no 477 2001 Coll as subsequently amended at EKO KOM a s The client number o...

Reviews: