Installation
(for qualified installers only)
17
© Travis Industries
4101110
100-01262_000
Rear Vent Configuration with Horizontal Termination
•
Use the rear vent conversion from Travis Industries (SKU 94400998).
•
Use 8” Diameter Vent
•
Horizontal sections require a ¼” (6mm) rise every 12” (305mm) of travel.
•
A maximum of three (3) 45° or 90° elbows may be used. Of these elbows, only one (1) may be a
horizontal elbow (see illustration).
•
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
position. NOTE: Restrictor positions are based upon lab tests. The ideal restrictor position may vary
slightly, especially when the termination is near a demarcation line
Exhaust Restrictor Position #5
Exhaust Restrictor Extender Installed
5 feet (1.5m)
10 feet (3m)
0 feet
5 feet (1.5m)
0 feet
0 feet
10 feet (3m)
0 feet
5 feet (1.5m)
10 feet (3m)
15 feet (4.5m)
16' max (4.8m)
Min. 1' (0.3m) Vertical Section Required
12 feet max (3.6m)
Exhaust Restrictor Removed
12 feet max (3.6m)
Exhaust Restrictor Position #3
Exhaust Restrictor Extender Installed
5 feet (1.5m)
10 feet (3m)
15 feet (4.5m)
16' max (4.8m)
Horizontal elbows are elbows placed between
two horizontal sections of pipe. One 45° or 90°
horizontal elbow is allowed for this configuration.
Horizontal Elbow