The RPL23 is entirely configurable in front face. Configuration access is done by pressing the top button.
For each configuration rubric, a message scrolls on display.
The top button (<YES>) allow to access to parameters setting of a relay or validate the corresponding function.
The bottom button (<NO>) allow to switch to the next rubric or disable the corresponding function.
When setting a parameter value, the top button allow to increment and the bottom button to decrement the value. While
setting, the display is blinking. Leaving the setting is automatic if no button is pressed for more than 4 seconds.
At the end of configuration, the message "
OK !
" is displayed and all parameters are memorized.
Configurable parameters are:
- Choice of AC or DC voltage measurement.
- Network type, single phase or three phases.
- Nominal line voltage (star voltage in three phases, L1/N voltage in single phase AC or L1/L2 voltage in DC).
- Associate alarms to relay 1 and 2.
- Activation and deactivation delays for relay 3 (phase order).
For each relay, it is possible to configure:
- Under voltage, overvoltage, asymmetry (three phases) and under/over frequency (AC) thresholds and activation/
deactivation delays.
- Enabling / disabling the 'HOLD' function (alarm memorised).
Note:
When "HOLD" function is activated, the alarm is memorized, 2 conditions are necessary to disable it:
- Make disappear the default that caused the alarm.
- Push the alarm acknowledge button (bottom button). A bip confirms the acknowledge.
1) Network parameters
Display message:
NETWORK (Y/N)?
The top button allow access to configuration of the network parameters, the bottom button allow to move to the nominal
voltage rubric.
1.1) Alternative voltage measurement (AC)
Display message:
AC VOLTAGE (Y/N)?
The top button validates the choice, the bottom button toggles to the DC voltage choice.
1.2) Continuous voltage measurement (DC)
Display message:
DC VOLTAGE (Y/N)?
The top button validates the choice, the bottom button toggles to the AC voltage choice.
Note:
If the user has selected the continuous mode (DC), the three phases / single phase rubrics are no longer accessible.
In this mode the device measures the continuous voltage present between L1 and L2 (see wiring p11).
1.3) Three phase network
Display message:
THREE PHASES (Y/N)?
The top button validates the choice, the bottom button toggles to the single phase choice.
1.4) Single phase network
Display message:
SINGLE PHASE (Y/N)?
The top button validates the choice, the bottom button toggles to the three phases choice.
2) Nominal voltage
Display message:
NOMINAL VOLTAGE
The value can be set between 50V (high voltage version) or 12 V (low voltage version) and 1600 V.
3) Relay #1
Display message:
RELAY #1 (Y/N)?
The top button allows access to configuration of relay 1, the bottom button allows to move to the relay 2 rubric.
Configuration