TABLE OF CONTENTS

 

 E 5 

The RPL23 is entirely configurable in front face. Configuration access is done by pressing the top button. 
For each configuration rubric, a message scrolls on display. 
The top button (<YES>) allow to access to parameters setting of a relay or validate the corresponding function. 
The bottom button (<NO>) allow to switch to the next rubric or disable the corresponding function. 
 
When setting a parameter value, the top button allow to increment and the bottom button to decrement the value. While 
setting, the display is blinking. Leaving the setting is automatic if no button is pressed for more than 4 seconds. 
 
At the end of configuration, the message "

OK !

" is displayed and all parameters are memorized. 

 
Configurable parameters are: 
- Choice of AC or DC voltage measurement. 
- Network type, single phase or three phases. 
- Nominal line voltage (star voltage in three phases, L1/N voltage in single phase AC or L1/L2 voltage in DC). 
- Associate alarms to relay 1 and 2. 
- Activation and deactivation delays for relay 3 (phase order). 
 
For each relay, it is possible to configure: 
- Under voltage, overvoltage, asymmetry (three phases) and under/over frequency (AC) thresholds and activation/ 
  deactivation delays. 
- Enabling / disabling the 'HOLD' function (alarm memorised). 
 

Note:

 

When "HOLD" function is activated, the alarm is memorized, 2 conditions are necessary to disable it: 

 

 

- Make disappear the default that caused the alarm. 

 

 

- Push the alarm acknowledge button (bottom button). A bip confirms the acknowledge. 

 
 

1) Network parameters 

Display message: 

NETWORK (Y/N)? 

The top button allow access to configuration of the network parameters, the bottom button allow to move to the nominal 
voltage rubric. 
 

1.1) Alternative voltage measurement (AC) 

Display message: 

AC VOLTAGE (Y/N)? 

The top button validates the choice, the bottom button toggles to the DC voltage choice. 
 

1.2) Continuous voltage measurement (DC) 

Display message: 

DC VOLTAGE (Y/N)? 

The top button validates the choice, the bottom button toggles to the AC voltage choice. 
 

Note: 

If the user has selected the continuous mode (DC), the three phases / single phase rubrics are no longer accessible. 
In this mode the device measures the continuous voltage present between L1 and L2 (see wiring p11). 

 
1.3) Three phase network 

Display message: 

THREE PHASES (Y/N)? 

The top button validates the choice, the bottom button toggles to the single phase choice. 

 
1.4) Single phase network 

Display message: 

SINGLE PHASE (Y/N)? 

The top button validates the choice, the bottom button toggles to the three phases choice. 
 

2) Nominal voltage 

Display message: 

NOMINAL VOLTAGE

 

The value can be set between 50V (high voltage version) or 12 V (low voltage version) and 1600 V. 
 

3) Relay #1 

Display message: 

RELAY #1 (Y/N)? 

The top button allows access to configuration of relay 1, the bottom button allows to move to the relay 2 rubric. 
 

 
Configuration 

Summary of Contents for RPL23

Page 1: ...Y LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ CEDEX 3 Phone 03 87 76 32 51 Contact Commercial Loreme fr Technique Loreme fr Download manual at www loreme fr CONFIGURATION HAN...

Page 2: ...p6 5 1 Under voltage alarm p6 5 2 Overvoltage alarm p6 5 3 Phase asymmetry alarm p6 5 4 Under frequency alarm p6 5 5 Over frequency alarm p7 5 6 HOLD function p7 6 Relay 3 p7 7 Special functions p7 8...

Page 3: ...nction Fault indication by falling output relay Power supply voltage LED Faults LEDs phases sequence error under over voltage under over frequency phase failure Alphanumeric 4 digits display for measu...

Page 4: ...f Over V and Under V LEDs are off Phases order LED is off C1 T1 and or C2 T2 contacts are closed The L1 N RMS input voltage or the L1 L2 DC voltage is displayed In case of overvoltage over frequency A...

Page 5: ...morized 2 conditions are necessary to disable it Make disappear the default that caused the alarm Push the alarm acknowledge button bottom button A bip confirms the acknowledge 1 Network parameters Di...

Page 6: ...allows to move to the next rubric Displayed message THRESHOLD Threshold setting from 0 to 99 No to disable the overvoltage detection Note If the threshold is set to 99 they will be no overvoltage det...

Page 7: ...m button leaves the configuration The configurable parameters are the alarm activation and deactivation delays The relay is in alarm if the phase order is not correct and is out of alarm if the phase...

Page 8: ...To access the configuration just press the top button The message RELAY 1 is displayed The top button YES provides access to its configuration the bottom button NO jump to the relay 2 rubric For the t...

Page 9: ...CTIVATION DELAY DEACTIVATION DELAY The top button YES provides access to the configuration of the parameter the bottom button NO jump to the next rubric In the case of YES choice the actual parameter...

Page 10: ...relays thyristor power groups Do not get closer within fifty centimeters of a device with a transmitter walkie talkie of a power of 5 W be cause the latter can create a field with an intensity higher...

Page 11: ...Common relay contact T3 T2 T1 terminals Work relay contact L1 terminal Phase 1 voltage input L2 terminal Phase 2 voltage input L3 terminal Phase 3 voltage input N terminal Neutral input optional For a...