4) Relay #2 

Display message: 

RELAY #2 (Y/N)? 

The top button allows access to configuration of relay 2, the bottom button allows to move to the relay 3 rubric. 

 
5) Configurable alarms parameters for the relays 
5.1) Under voltage alarm 

Display message: 

UNDERVOLTAGE CONFIG. (Y/N)? 

The top button allows access to configuration, the bottom button allows to move to the next rubric. 
 
Displayed message: 

THRESHOLD 

Threshold setting from 0 to -99%, ‘No’ to disable the under voltage detection. 
The minimum measured voltage is 10 V (high voltage version) or 2.5V (low voltage version). Beneath this value, the 
measured voltage is zero. The voltages are given between phase and neutral. 
 

Note:

 If the threshold is set to -99 %, they will be no undervoltage detection.  

 
Displayed message: 

ACTIVATION

 

DELAY 

Delay setting from 0 to 600 s by 0,2 s steps between 0 and 100 s and 1 s up to 600 s. 
 
Displayed message: 

DEACTIVATION

 

DELAY 

Delay setting from 0 to 600 s by 0,2 s steps between 0 and 100 s and 1 s up to 600 s. 
 

5.2) Overvoltage alarm 

Display message: 

OVERVOLTAGE CONFIG. (Y/N)? 

The top button allows access to configuration, the bottom button allows to move to the next rubric. 
 
Displayed message: 

THRESHOLD 

Threshold setting from 0 to 99%, ‘No’ to disable the overvoltage detection. 
 

Note:

 If the threshold is set to 99 %, they will be no overvoltage detection. 

 

 
Displayed message: 

ACTIVATION

 

DELAY 

Delay setting from 0 to 600 s by 0,2 s steps between 0 and 100 s and 1 s up to 600 s. 
 
Displayed message: 

DEACTIVATION

 

DELAY 

Delay setting from 0 to 600 s by 0,2 s steps between 0 and 100 s and 1 s up to 600 s. 
 

5.3) Phase asymmetry alarm 

Display message: 

ASYMMETRY CONFIG. (Y/N)? 

The top button allows access to configuration, the bottom button allows to move to the next rubric. 
 
Displayed message: 

THRESHOLD

 

Threshold setting from 0 to 99%, ‘No’ to disable the asymmetry detection. 
 

Note:

 If the threshold is set to 99 %, they will be no asymmetry detection. 

 

 
Displayed message: 

ACTIVATION

 

DELAY 

Delay setting from 0 to 600 s by 0,2 s steps between 0 and 100 s and 1 s up to 600 s. 
 
Displayed message: 

DEACTIVATION

 

DELAY 

Delay setting from 0 to 600 s by 0,2 s steps between 0 and 100 s and 1 s up to 600 s. 
 

5.4) Under frequency alarm 

Display message: 

UNDERFREQUENCY CONFIG. (Y/N)? 

The top button allows access to configuration, the bottom button allows to move to the next rubric. 
 
Displayed message: 

THRESHOLD 

Threshold setting from 70 Hz to 5 Hz, ‘No’ to disable the under frequency detection. 
 
Displayed message: 

ACTIVATION

 

DELAY 

Delay setting from 0 to 600 s by 0,2 s steps between 0 and 100 s and 1 s up to 600 s. 

Summary of Contents for RPL23

Page 1: ...Y LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ CEDEX 3 Phone 03 87 76 32 51 Contact Commercial Loreme fr Technique Loreme fr Download manual at www loreme fr CONFIGURATION HAN...

Page 2: ...p6 5 1 Under voltage alarm p6 5 2 Overvoltage alarm p6 5 3 Phase asymmetry alarm p6 5 4 Under frequency alarm p6 5 5 Over frequency alarm p7 5 6 HOLD function p7 6 Relay 3 p7 7 Special functions p7 8...

Page 3: ...nction Fault indication by falling output relay Power supply voltage LED Faults LEDs phases sequence error under over voltage under over frequency phase failure Alphanumeric 4 digits display for measu...

Page 4: ...f Over V and Under V LEDs are off Phases order LED is off C1 T1 and or C2 T2 contacts are closed The L1 N RMS input voltage or the L1 L2 DC voltage is displayed In case of overvoltage over frequency A...

Page 5: ...morized 2 conditions are necessary to disable it Make disappear the default that caused the alarm Push the alarm acknowledge button bottom button A bip confirms the acknowledge 1 Network parameters Di...

Page 6: ...allows to move to the next rubric Displayed message THRESHOLD Threshold setting from 0 to 99 No to disable the overvoltage detection Note If the threshold is set to 99 they will be no overvoltage det...

Page 7: ...m button leaves the configuration The configurable parameters are the alarm activation and deactivation delays The relay is in alarm if the phase order is not correct and is out of alarm if the phase...

Page 8: ...To access the configuration just press the top button The message RELAY 1 is displayed The top button YES provides access to its configuration the bottom button NO jump to the relay 2 rubric For the t...

Page 9: ...CTIVATION DELAY DEACTIVATION DELAY The top button YES provides access to the configuration of the parameter the bottom button NO jump to the next rubric In the case of YES choice the actual parameter...

Page 10: ...relays thyristor power groups Do not get closer within fifty centimeters of a device with a transmitter walkie talkie of a power of 5 W be cause the latter can create a field with an intensity higher...

Page 11: ...Common relay contact T3 T2 T1 terminals Work relay contact L1 terminal Phase 1 voltage input L2 terminal Phase 2 voltage input L3 terminal Phase 3 voltage input N terminal Neutral input optional For a...

Reviews: