SOMMAIRE

 

 E 7 

 
RS232 link setting 

Enter name for the new 
connection 

Start a "hyper Terminal" connection : 
- Click on 

"START" 

button 

 

Up to XP version 
- Go to 

"Programs \ Accessories \ Communication \ Hyper Terminal"

 

- Click on 

"Hypertrm.exe" 

Or if the software was downloaded 
- Go to 

"All programs \ HyperTerminal Private Edition"

 

- Click on 

"HyperTerminal Private Edition" 

     Choose: 
- 9600 bauds 
- 8 DATA bits 
- no parity 
- 1 stop bit 

XON/XOFF

 

The device can be configured or updated in terminal mode via an RS232 link. 
 

Step 1: Driver installation for USB / RS232 adapter

 

 

 - download driver at www.loreme.fr:  
 

http://www.loreme.fr/aff_produits.asp?rubid=53&langue=fr

 

 
 - Click on executable file to install the driver, 
 - Plug the cable on a USB port, Windows install a new serial communication port 

COMx

 

(x >= 4). 

 
Note :  

The use of the cable on another USB port don’t generates a new communication port. 
Use of another adapter generates another communication port number (COMx) and re-
quires the reconfiguration of the hyperterminal. 

The terminal emulation software for PC « HyperTerminal » is resident in windows up to XP version. For later ver-
sions, it is downloadable on : 

www.loreme.fr in download part

 ( 

http://www.loreme.fr/HyperTerm/htpe63.exe

 ) 

 
=> Run the downloaded software to install it.

 

1

 

Step 2: Setting of terminal emulation software (PC with windows). 

2

 

3

 

4

 

5

 

Choose the communication port  
related to the adapter. 

The PC is now in terminal mode, connect it to the device by plugging the RS232 cable. The measure is now dis-

played on the terminal. To access configuration, press ’

C

’ key. 

6

 

7

 

Note

: to modify the parameters of terminal mode whereas this one is already started, it is necessary, after having car-

ried out the modifications, to close the terminal and to open it again so that the modifications are effective. 

When leaving Hyper terminal, the following window will  
 

 

 

 

appear. By saving, the terminal  

 

 

 

 

session will start with the same  

 

 

 

 

configuration. 

Thus, the shortcut  

will permit to communi-

cate with all LOREME devices. 

Summary of Contents for RPS23

Page 1: ...LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ CEDEX 3 Phone 03 87 76 32 51 Telefax 03 87 76 32 52 Contact Commercial Loreme fr Technique Loreme fr Download manual at www loreme...

Page 2: ...E PRESENTATION p3 CONFIGURATION p3 1 Thermal protection configuration p4 2 Relays configuration p5 3 Analog outputs configuration p6 RS232 LINK SETTING p7 FIRMWARE UPDATE p8 EMC CONSIDERATION p9 1 Int...

Page 3: ...3 3 relays idem R2 nominal current overflow alarm RPS23 R4 4 relays idem R3 watchdog RPS23 S1 1 insulated analog output RPS23 S2 2 insulated analog outputs independently configurable The technical dat...

Page 4: ...ment it is necessary to filter the input signal This parameter is the coefficient of the digital filter included in the device By increasing the value the response time of the filter is increased and...

Page 5: ...and 2 and in of the nominal current for relay 3 The security parameter allows to choose between the activation or the de activation of the relay when alarm is activated in positive security relay is s...

Page 6: ...ime The security value allows to set the output to a known state when there is a sensor breaking or a measure range over flow This value will be transferred to output The limitation allows to bound th...

Page 7: ...another communication port number COMx and re quires the reconfiguration of the hyperterminal The terminal emulation software for PC HyperTerminal is resident in windows up to XP version For later ve...

Page 8: ...mode and is waiting for the firmware file This file is provide by LOREME and contain the firmware code in Intel HEX format Select the Transfer Send a text file in the HyperTerminal menu Select the dir...

Page 9: ...ty centimeters of a device with a transmitter walkie talkie of a power of 5 W be cause the latter can create a field with an intensity higher than 10 V M for a distance fewer than 50 cm 2 2 Power supp...

Page 10: ...rminal A terminal E external shunt Analog output 1 terminal K terminal L Terminals K shunt must be closed for voltage output Analog output 2 terminal P terminal N Terminals P shunt must be closed for...

Page 11: ...N CONFIG BP UP Up button Yes Down button No Yes Yes No No NOMINAL CURRENT XXXX value adjustment with UP DOWN buttons Yes No MEASURE FILTER XXXX value adjustment with UP DOWN buttons Yes No K COEFFICIE...

Page 12: ...03 87 76 32 52 Email Commercial Loreme fr Techni Next Page Up button Yes Down button No a COEFFICIENT XXXX value adjustment with UP DOWN buttons Yes No b COEFFICIENT XXXX value adjustment with UP DOWN...

Page 13: ...URITY NEGATIVE SECURITY ACTIVATION DELAY Value Setting Yes No DEACTIVATION DELAY Value Setting Yes No Yes OK Yes Yes Yes OUTPUT CONFIGURATION CURRENT VOLTAGE Low and high scale adjustment block OUTPUT...

Reviews: