4 Specifications and DC Disconnect Switch
3
Specifications
Table 1:
Specifications
Product Name
Powerpack 600S
Item No.
19-005300
19-005305
Grid connection
CEE 7/7
NEMA 5-15P
Pump system
PS2-200 / PS2-600
AC In
100-260 V AC / 50-60 Hz
DC Out
56 V 10.5 A
PV In
max. 150 V DC
Working Temp
-30 ≈ + 50°C (start derating ≈+40°C)
IP Class
IP23
3.1 Application
Some solar pumps may not provide
sufficient flow under all conditions. The
LORENTZ PowerPack PP600S allows the
pump to be powered by an AC mains
supply such as a grid or generator.*
For switching between solar and back-
up power, the PV generator must be
switched off with a PV Disconnect. If this
is not done, the pump controller will con-
tinue to run on solar until the voltage of
solar drops below PowerPack voltage. For
a scheduled use of the PowerPack (e.g. to
extend pumping time) a separate (timer)
switch can be used to control the power
supply to the PowerPack. If the auxiliary
power source is switched off, the Power
-
Pack automatically returns to solar-direct
operation (if the PV is switched on).
* Running the pump with a PowerPack
will reduce the maximum speed of the
pump in some applications.
3.2 Which Powerpack should be used?
The PP600S should be used for the
PS-200/PS2-200/PS-600 and PS2-600
controller. In some applications it may
be necessary to use the PP600H for the
PS2-600.
Use COMPASS/partnerNET to check which
PowerPack is suitable for the application.