I433 GB I 06 15
31100216
3
INSTALLATION
Modem
– PMVFGSM1 can be mounted on DIN rail (EN 50022)
– The installation must ensure IP40 protection degree minimum
– For electrical connection, refer to the wiring diagram and to specification in the electrical
characteristics, described in the dedicated sections.
SIM card
– We recommend to insert the SIM card in a telephone to disable the PIN request: it will be possible to
protect the card managing the PIN number directly with PMVF GSM1 SW software. Inserting a SIM
card with PIN different than the one set in the device, the system does not work. In that situation, if
the modem is powered three times, the SIM card is blocked; to unlock the SIM card the PUK code is
required as normally done with cell phones
– Unplug the USB cable and, if the blue led stays ON, the battery (see note at the end of the manual)
before inserting or removing the SIM card
– Use 3V or 1.8V SIM card only.
INSTALLAZIONE
Modem
– PMVFGSM1 è adatto al montaggio su guida DIN EN 50022 o in centralini modulari.
– L’installazione deve garantire un grado di protezione minimo IP40.
– Per i collegamenti elettrici fare riferimento agli schemi di connessione riportati nell’apposito capitolo e
alle prescrizioni riportate nella tabella delle caratteristiche tecniche.
SIM card
– Inserire la SIM card in un telefono e disabilitare il PIN: si potrà proteggere la scheda successivamente
riabilitando il PIN con il tool software del modem accedendo al terminale. Infatti, inserendo una SIM
card con PIN diverso da quello impostato nel dispositivo, il sistema non funzionerà. In questa
situazione, se il modem viene acceso per 3 volte, la SIM viene bloccata; per sbloccarla è necessario il
codice PUK come avviene nell’utilizzo con un telefono.
– Scollegare il cavo USB e, se il led blu rimane acceso, la batteria (vedi istruzioni in fondo al manuale)
prima di inserire o rimuovere la carta SIM.
– Inserire SIM card da 3V o 1,8V.
13 14 15 16 17 18
19 20
+
COM
-
IN1 IN2 IN3 IN4
DIGITAL INPUTS
❷
PMVF GSM 1
DDI FEEDBACK
DDI FEEDBACK
SPI EXCLUSION
LOCAL CONTROL
REMOTE
DISCONNECTION
12...24VAC/DC
AUXILIARY
SUPPLY
PMVF30
SLOT 2
EXP10 00
9.5-3.5V
9.5-27V
=
13 14 15 16 17 18
19 20
+
COM
-
IN1 IN2 IN3 IN4
INGRESSI DIGITALI
❷
PMVF GSM 1
FEEDBACK DDI
FEEDBACK DDI
ESCLUSIONE SPI
COMANDO LOCALE
TELESCA
TTO
ALIMENTAZIONE
AUSILIARIA
PMVF30
SLOT 2
EXP10 00
12...24VAC/DC
9,5-3,5V
9,5-27V
=
Wiring diagram for PMVF30 and modem connection
Schema di collegamento con PMVF30
Schema di collegamento con altre protezioni di interfaccia (PI) con ingresso di teledistacco
autoalimentato
DDI
PI CEI-016
Alimentazione
ausiliaria
Comando chiusura
DDI e teledistacco
Chiusura DDI e
teledistacco
Contatto ausiliario
del DDI
Ingresso digitale
programmato come
teledistacco
13 14 15 16 17 18
19 20
PMVF GSM 1
ALIMENTAZIONE
AUSILIARIA
+Vaux
+Vaux
-Vaux
-Vaux
12...24VAC/DC
9,5-3,5V
9,5-27V
=
Wiring diagram with other interface protection (PI) with self-powered remote disconnection
DDI
PI CEI-016
Auxiliary
supply
DDI closing command
and remote disconnection
DDI closing and
remote disconnection
Auxiliary contact
of DDI
Digital input as
remote disconnection
13 14 15 16 17 18
19 20
PMVF GSM 1
AUXILIARY
SUPPLY
+Vaux
+Vaux
-Vaux
-Vaux
12...24VAC/DC