Doc: I562EGB07_18 ok.docx 13/09/2018
p. 6 / 17
B
Desactivación retardada del relé
Parámetro
Descripción
Modo de reinicio
P01.06
No produce efecto (con independencia de que se configure en INP o PWR; para reanudar la
función es preciso apagar y volver a encender el temporizador).
Contador predefinido
P02.01
No produce efecto (tras T1, la salida permanece desactivada hasta que se desconecta la
alimentación del temporizador).
B
Off delay
Parameter
Description
Reset mode
P01.06
This parameter has no effect (independently from the setting INP or PWR, to restart the
function is necessary to turn off and on the power supply of the timer).
Preset counter
P02.01
This parameter has no effect (after the time T1 the output remains de-energised until you
remove the power supply to the timer).
Bt
Desactivación retardada del relé con opción de pausa mediante
contacto
Parámetro
Descripción
Modo de reinicio
P01.06
No produce efecto (con independencia de que se configure en INP o PWR; para reanudar la
función es preciso apagar y volver a encender el temporizador).
Contador predefinido
P02.01
No produce efecto (tras T1, la salida permanece desactivada hasta que se desconecta la
alimentación del temporizador).
Bt
Off delay with optional pause with contact
Parameter
Description
Reset mode
P01.06
This parameter has no effect (independently from the setting INP or PWR, to restart the
function is necessary to turn off and on the power supply of the timer).
Preset counter
P02.01
This parameter has no effect (after the time T1 the output remains de-energised until you
remove the power supply to the timer).
C
Intermitencia, inicio OFF, ciclos asimétricos
Parámetro
Descripción
Modo de reinicio
P01.06
No produce efecto (con independencia de que se configure en INP o PWR; para reanudar la
función es preciso apagar y volver a encender el temporizador).
Contador predefinido
P02.01
Cuando la salida de relé se cierra tantas veces como se ha configurado en P02.01, el
temporizador permanece "bloqueado". Para realizar de nuevo la función hay que apagar y
volver a encender el temporizador. Predeterminado = OFF (ciclos ilimitados).
Ejemplo: con P02.01=3, la salida realiza 3 ciclos de pausa/trabajo (T1-T2, T1-T2, T1-T2) tras
encender el temporizador. Cuando terminan, la salida se desactiva y permanece así hasta
que se apaga y se vuelve a encender el temporizador.
C
Flasher, starting with OFF, asymmetrical timings
Parameter
Description
Reset mode
P01.06
This parameter has no effect (independently from the setting INP or PWR, to restart the
function is necessary to turn off and on the power supply of the timer).
Preset counter
P02.01
When the number of the closures of the relay output reaches the value set in P02.01, the
timer goes into a “lock” status and is no longer possible to perform the function . To restart to
perform the function is necessary to turn off and on the power supply of the timer. Default =
OFF (infinite cycles).
Example: with P02.01=3, once the timer is supplied the relay outputs performs 3 cycles (T1-
T2, T1-T2, T1-T2), at the end of which the relay output de-energises and remains de-
energised until you turn off and on the power supply of the timer.
Ct
Intermitencia, inicio OFF, ciclos asimétricos, con opción de
pausa mediante contacto
Parámetro
Descripción
Modo de reinicio
P01.06
No produce efecto (con independencia de que se configure en INP o PWR; para reanudar la
función es preciso apagar y volver a encender el temporizador).
Contador predefinido
P02.01
Cuando la salida de relé se cierra tantas veces como se ha configurado en P02.01, el
temporizador permanece "bloqueado". Para realizar de nuevo la función hay que apagar y
volver a encender el temporizador. Predeterminado = OFF (ciclos ilimitados).
Ejemplo: con P02.01=3, la salida realiza 3 ciclos de pausa/trabajo (T1-T2, T1-T2, T1-T2) tras
encender el temporizador. Cuando terminan, la salida se desactiva y permanece así hasta
que se apaga y se vuelve a encender el temporizador.
Ct
Flasher, starting with OFF, asymmetrical timings, with optional
pause with contact
Parameter
Description
Reset mode
P01.06
This parameter has no effect (independently from the setting INP or PWR, to restart the
function is necessary to turn off and on the power supply of the timer).
Preset counter
P02.01
When the number of the closures of the relay output reaches the value set in P02.01, the
timer goes into a “lock” status and is no longer possible to perform the function . To restart to
perform the function is necessary to turn off and on the power supply of the timer. Default =
OFF (infinite cycles).
Example: with P02.01=3, once the timer is supplied the relay outputs performs 3 cycles (T1-
T2, T1-T2, T1-T2), at the end of which the relay output de-energises and remains de-
energised until you turn off and on the power supply of the timer.