M02 - UTILITY UdM Default Range
P02.01 Language English English
Italiano
Francais
Espanol
Portoguese
P02.02 Display contrast % 50 0-100
P02.03 High backlight level % 100 0-100
P02.04 Low backlight level % 30 0-50
P02.05 Low backlight delay sec 30 5-600
P02.06 Default page return sec 60 OFF / 10-600
P02.07 Default page VL-L VL-L / VL-N ...
P02.08 Default sub-page INST INST / HI / LO /
AVG / MD /GRAPH /
1-8
P02.09 Display update time sec 0.5 0.1 - 5.0
P02.06
– If set to OFF the display always remains in the page where the user left it. If set to a time delay, after that time the display page goes back to page set in P02.07.
P02.07
– Number of the page to which the display returns automatically after time specified by P02.06 has elapsed from the last keystroke.
P02.08
– Sub-page type to which the display returns after P02.06 has elapsed.
P03.01
– If set to OFF, password management is disabled and the access to setup parameters and command menu is allowed.
P03.02
– When P.03.01 enabled, value to be specified to get user access. Refer to Password Access chapter.
P03.03
– Like P03.02, but referred to advanced access.
M03 - PASSWORD UdM Default Range
P03.01 Enable passwords OFF OFF-ON
P03.02 User level password 1000 0-9999
P03.03 Advanced level password 2000 0-9999
P04.01
– Selection of average reading calculation method:
Fixed
= Readings are integrated for the set time. Every time the integration time elapses, the Average value is updated with the result of the last integration.
Shift
= The instantaneous values are integrated for a period of time equal to 1/15th of the set time. Every time this interval elapses, the oldest value is replaced with the new one just calculated. The average value is
updated every 1/15th of the time set, considering a time-sliding window that groups the last 15 calculated values, with a total length equal to integration time setting.
Sync
= Like fixed mode, but the integration intervals are started by an external digital input programmed with Synchronisation function.
Bus
= Like fixed mode, but the integration intervals are started by synchronising messages on the serial bus.
P04.02
– Average readings integration time, used for active, reactive and apparent power.
P04.03, P04.04, P04.05
– Readings integration time (AVG) for the corresponding measurements.
M04 - INTEGRATION UdM Default Range
P04.01 Integration mode Shift Fixed / Shift
Sync. / Bus
P04.02 Power integration time min 15 1-60
P04.03 Current integration time min 15 1-60
P04.04 Voltage integration time min 1 1-60
P04.05 Frequency integration time min 1 1-60
P05.01
– If set to OFF the hour counters are disabled and the hour meter page is not shown.
P05.02
– If set to OFF, the partial hour counter is not incremented. If ON, time is incremented as long as DMG is powered. If set to an internal variable (INPx-LIMx-BOOx), time increments only while a programmed
condition occurs.
P05.03
– Number of the channel (x) of the variable eventually used in the previous parameter. Example: If the partial hour counter must count the time during which one measurement is above a certain threshold, e.g.
defined by LIM3, then it is necessary to program LIMx in the previous parameter and channel 3 in this parameter.
M05 - HOUR COUNTER UdM Default Range
P05.01 Hour counter enable ON OFF-ON
P05.02 Partial hour counter enable ON OFF-ON- INPx-
LIMx-BOOx
P05.03 Channel number (x) 1 1-8
P06.01
– Selects the reading to be shown on trend graph page.
P06.02
– Choice between automatic range or fixed range defined by the user.
P06.03
– Full scale range value. The unit of measure is the one defined by the selected reading.
P06.04
– Full scale value multiplier.
M06 - TREND GRAPH UdM Default Range
P06.01 Trend graph measurement kW (tot) VL-L (eq) AVG
AVG kW (tot) AVG
kvar (tot) AVG
kVA (tot) AVG
P06.02 Autorange ON OFF-ON
P06.03 Full scale value 1000 0-1000
P06.04 Full scale multiplier x1 x1 - x1k - x1M