M14 - OUTPUTS UdM Default Range
P14.n.01 Output function OFF OFF-ON-SEQ-LIMx-
BOOx-ALAx-PULx-
REMx
P14.n.02 Channel number (x) 1 1 - 8
P14.n.03 Idle status OFF OFF-ON
Note:
This menu is divided into 8 sections, for digital outputs OUT1..8
P14.n.01
= Function of the output:
OFF
– Output disabled
ON
– Output always enabled
SEQ
– Output enabled in case of wrong phase sequence
LIMx – BOOx – ALAx – PULx – REMx
– Output linked to the status of the programmed variable. Allows to connect the status of an output to the status of a limit threshold, a Boolean variable, an alarm, etc.
P14.n.02
= Number of the channel (x) referred to previous parameter.
P14.n.03
= Normal status of the output. Allows to reverse the logic of the output function.
M15 - USER-DEFINED PAGES Default Range
P15.n.01 Page enabling OFF OFF - ON
P15.n.02 Title PAGn (Text - 16 char)
P15.n.03 Measurement 1 OFF OFF- (measurements)
P15.n.04 Measurement 2 OFF OFF- (measurements)
P15.n.05 Measurement 3 OFF OFF- (measurements)
P15.n.06 Measurement 4 OFF OFF- (measurements)
Note:
This menu is divided into 4 sections, for user pages PAG1..4
P15.n.01
= Enables user page PAGn.
P15.n.02
= Title of the user page. Free text, 16 chars.
P15.n.03, P15.n.04, P15.n.05, P15.n.06
= Measurement that will be shown in the four frames of the user page.
COMMANDS MENU
– The commands menu allows executing some occasional operations like reading peaks resetting, counters clearing, alarm reset, etc.
– If the Advanced level password has been entered, then the commands menu allows executing the automatic operations useful for the device configuration.
– The following table lists the functions available in the commands menu, divided by the access level required.
Code COMMAND ACCESS LEVEL DESCRIPTION
User Advanced
C.01 RESET HI-LO
Clears of HI and LO peaks of all readings
C.02 MAX DEMAND RESET
Clears of Max Demand of all readings
C.03 PARTIAL ENERGY METER RESET
Clears partial Energy meters
C.04 PARTIAL HOUR COUNTERS RESET
Clears partial hour counters
C.05 RESET COUNTERS
Clears counters
C.06 RESET TARIFFS
Clears tariff Energy meters
C.07 RESET ALARMS
Clears alarms with latch
C.08 RESET LIMITS
Clears limit thresholds with latch
C.11 TOTAL ENERGY METER RESET
Clears total, partial and tariff energy meters
C.12 TOTAL HOUR COUNTERS RESET
Clears total hour counters
C.13 PARAMETERS TO DEFAULT
All set-up parameters are reset to factory default value
C.14 PARAMETERS BACKUP
Saves a backup copy of all set-up parameters
C.15 PARAMETERS RESTORE
Restores the set-up parameters to backup values
C.16 WIRING TEST
Carries out the wiring test in order to check proper wiring
of the DMG. See wiring test chapter.
– Once the required command has been selected, press
to execute it. The device will prompt for a confirmation. Pressing
again, the command will be executed.
– To cancel the command execution press
MENU
.
– To quit commands menu press
MENU
.