10: Programmable outlets setting
Interface
Setting
Parameter 2:
Set up backup time limits for programmable
outlets.
0-999:
setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on
battery mode. (Default: 999)
•
11: Autonomy limitation setting
Interface
Setting
Parameter 2:
Set up backup time on battery mode for general
outlets.
0-999:
setting the backup time in minutes from 0-999 for
general outlets on battery mode.
DIS:
Disable the autonomy limitation and the backup time will
depend on battery capacity. (Default)
Note:
When setting as “0”, the backup time will be only 10 seconds.
•
12: Battery total AH setting
Interface
Setting
Parameter 2:
Set up the battery total AH of the UPS.
7-999:
setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external battery
bank is connected.
•
13: Maximum charger current setting
Interface
Setting
Parameter 2:
Set up the charger maximum current.
1/2/4/6/8:
setting the charger maximum current 1/2/4/6/8 in
Ampere. (Default: 2A)
Note:
Please set the appropriate charger current based on
battery capacity used. The recommended charging current is
0.1C~0.3C of battery capacity as following table for reference.
Battery capacity (AH)
Total charging current (A)
7~20
2
20~40
4
40~60
6
60~
8