Lowell UPS8 Series Manual
Pg. 20
00: Exit Setting
Steps for setting programmable outlet
Step 1:
Before entering setting mode, the UPS should be in Stand-by mode
(off-charging) and make sure the battery is connected . The LCD
display is shown at right .
Step 2:
Press and hold the “Select” button for 3 seconds to enter Setting
mode .
Step 3:
Press the “Up” button (ON/MUTE) to switch to “02” of program list .
Then press “Enter” button to enter value setting of parameter 2 .
Press the “Up” button to change the value to “ENA” to enable the
programmable outlet function . Then press “Enter” button again to
confirm the setting .
Step 4:
Press the “Up” button (ON/MUTE) again to switch to “03” of
program list . Then press “Enter” button for setting programmable
outlet time . Push “Up” button to change the value of backup time
desired . Then press “Enter” to confirm the setting .
Step 5:
Press “UP” button (ON/MUTE) to switch to “00” of program list . Then press “Enter” button to exit setting menu .
Step 6:
Disconnect AC input and wait until the LCD display is off . The new setting will be activated when turning the UPS on again .