Lowell UPS8 Series Manual
Pg. 3
IMPORTANT SAFETY WARNINGS
Please comply with all warnings and operating instructions in this manual strictly . Save this manual properly and read carefully
the following instructions before installing the unit . Do not operate this unit before reading through all safety information and
operating instructions carefully .
Transportation
• Transport the UPS system only in the original package to protect against shock and impact .
Preparation
• Condensation may occur if the UPS system is moved directly from cold to warm environment . The UPS system must be
absolutely dry before being installed . Allow at least two hours for the UPS system to acclimate to the environment .
• Do not install the UPS system near water or in moist environments .
• Do not install the UPS system where it would be exposed to direct sunlight or near heater .
• Do not block ventilation holes in the UPS housing .
Installation
• Do not connect appliances or devices which would overload the UPS system (e .g . laser printers) to the UPS output sockets .
• Place cables in such a way that no one can step on or trip over them .
• Do not connect domestic appliances such as hair dryers to UPS output sockets .
• The UPS can be operated by any individual with no previous experience .
• Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system .
• Use only VDE-tested, CE-marked mains cable (e .g . the mains cable of your computer) to connect the UPS system to the
building wiring outlet (shockproof outlet) .
• Use only VDE-tested, CE-marked power cables to connect the loads to the UPS system .
• When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices
does not exceed 3 .5mA .
• Temperature Rating: Units are considered acceptable for use in a maximum ambient temperature of 104˚F (40˚C) .
• For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall be easily accessible .
•
Caution
—the unit is heavy . Lifting the unit requires a minimum of two people .
• Check if there is a protection device against over current and short circuit in the upstream of the UPS system . The recommended
protection spec is 11A for 1100VA, 15A for 1500VA, 20A for 2000VA and 2200VA, and 30A for 3000VA with a B or C trip
curve .
Operation
• Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operation
since this would cancel the protective earthing of the UPS system and of all connected loads .
• The UPS system features its own internal current source (batteries) . The UPS output sockets or output terminals block may
be electrically live even if the UPS system is not connected to the building wiring outlet .
• In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains .
• Prevent fluids and other foreign objects from getting inside the UPS system .
• The EPO, RS-232 and USB circuits are an IEC 60950 safety extra low voltage (SELV) circuit . This circuit must be separated
from any hazardous voltage circuits by reinforced insulation .