9 Operating Interfaces
9.1 CEA-709 Interface
9.1.1 NV Import File
Network variables can be imported to the L-Proxy Configurator in a CSV file. The format
of this file is described in this section.
The first line of the file must contain a comment, starting with a hash character ‘#’
specifying the format version and import technology:
#dpal_csv_config;Version=1;Technology=CEA709
After that line any number of comment lines starting with the hash character ‘#’ are
allowed. Lines that are not comments specify one NV per line, using the column
information as described in Table 8. The columns are separated by commas ‘,’ or semi-
colons ‘;’. Which separator is used can be configured in the Web UI (see Section 5.2.1).