12 Troubleshooting
12.1 All port LEDs are flashing red
Problem
All port LEDs are flashing red at a rate of approximately once per second and the L-Proxy
does not relay messages.
Explanation
Somehow the primary image was destroyed and the fall-back image was booted (see
Section 9.1). This image does not support relaying messages. It only allows downloading
a new firmware.
Solution
If this problem occurs because a firmware update was attempted (and failed somehow),
simply retry downloading the new firmware image.
If no firmware update was attempted, please contact LOYTEC support (see Section 12.7).
12.2 LonMaker Warning appears during installation
Problem
When adding a new L-Proxy Port to the project the following warning messages might
appear.
Figure 154 Click OK to continue.