Terminal
Function
1 Earth
Ground
2, 3
CEA-709 A, B of FT Channel Port 2
4 Earth
Ground
5, 6
CEA-709 A, B of FT Channel Port 1
8 Ethernet
100Base-T
15 Earth
Ground
16, 17
Power Supply 12 – 35 VDC or 12 – 24 VAC ± 10 %
Do not connect terminal 17 to earth ground!
Table 3: L-Proxy Terminals LP-33E100.
3.8 Wiring
The CEA-709 network segment connected to the L-Proxy needs to be terminated according
to the rules found in the specification of the transceiver (see Section 10.1).
Important:
When using shielded network cables, only one side of the cable should be connected to
earth ground. Thus, the shield must be connected to earth ground either at the L-Proxy
terminals or somewhere else in the network.
Important:
Never connect terminal 17 to earth ground!
Ethernet
Power Supply
Figure 8: Connecting the L-Proxy