L-Proxy User Manual
37
LOYTEC
Version 3.1
LOYTEC electronics GmbH
Data Point Menu
=================================
[1] Data Points
[2] Get Value
[3] Set Value
[q] Quit without saving
Please choose:
Figure 28: L-Proxy Data Point Menu.
4.10.1 Option 1 – List Data Points
Select this option to list all data points on the L-Proxy. The list is flat and displays the
values and status of each data point. An example is shown in Figure 29.
Data Points:
----------------------------------------
CEA709 Port: (node)
NV_node1Ctrlnvi17state_bit0: invalid value (input) invalid value
NV_node1Ctrlnvo16state_bit0: 0 (output)
NV_node1Ctrlnvi15fire_test: invalid value (input) invalid value
NV_node1Ctrlnvo14fire_test: 2 (output)
NV_node1Ctrlnvi13amp: invalid value (input) invalid value
NV_node1Ctrlnvo12amp: -773.200000 (output)
CEA709 Port: (node)
-> NV_node1Ctrlnvi17state: invalid value (output) inactive
bit0: invalid value (output) invalid value
-> NV_node1Ctrlnvo16state: 8000000000000000 (input) inactive
bit0: 1 (input)
NV_node1Ctrlnvi15fire_test: invalid value (output) invalid value
NV_node1Ctrlnvo14fire_test: 2 (input)
NV_node1Ctrlnvi13amp: invalid value (output) invalid value
NV_node1Ctrlnvo12amp: -773.200000 (input)
Figure 29: Example data point listing.
4.10.2 Option 2 – Get Value
This option allows retrieving the value of a specific data point. When selecting this option
the user is prompted to enter the complete data point name, e.g., ‘NV_node1Ctrlnvi13amp’.
Then hit
Enter
.
4.10.3 Option 3 – Set Value
This option allows setting the value of a specific data point. When selecting this option the
user is prompted to enter the complete data point name, e.g., ‘NV_node1Ctrlnvi13amp’.
Then hit
Enter
and enter the desired value when prompted and press
Enter
again.