L-Proxy User Manual
40
LOYTEC
Version 3.1
LOYTEC electronics GmbH
information such as calendar data. (3)
admin
has full access to the L-Proxy and can make
changes to its configuration. Note that the user accounts are also used to log on to the FTP
and Telnet server.
Figure 32: Password Configuration Screen
Please change the administrator password in order to protect yourself from unwanted
configuration changes by anyone else. To do so, select the
admin
account in the drop-
down box and enter the new password. If the administrator password is left empty,
password protection is turned off and everyone can access the L-Proxy without entering a
password. Click on
Change password
to activate the change.
5.2 Device Configuration
The device configuration pages allow viewing and changing the device settings of the L-
Proxy. Here are some general rules for setting IP addresses, port numbers, and time values:
•
An empty IP address field disables the entry.
•
An empty port number field sets the default port number.
•
An empty time value field disables the time setting.
5.2.1 System Configuration
The system configuration page is shown in Figure 33. This page allows to configure the L-
Proxy’s system time. The time sync source can be set to
auto
,
manual
,
NTP
, or
LonMark
. In the
auto
mode, the device switches to the first external time source that is
discovered. The option
manual
allows setting the time manually in the fields
Local Time
and
Local Date
. In
manual
mode, the device does not switch to an external time source.
Note, that if
NTP
is selected, the NTP servers have to be configured in the IP
Configuration page (see Section 5.2.2).
The time zone offset must be defined independently of the time source. It is specified as the
offset to GMT in hours and minutes (e.g., Vienna/Austria is +01:00, New York/USA is
-06:00). For setting the daylight saving time (DST) predefined choices are offered for
Europe and USA/Canada. DST can be switched off completely by choosing
none
or set
manually for other regions. In that case, start and end date of DST must be entered in the
fields below.