L-Proxy User Manual
67
LOYTEC
Version 3.1
LOYTEC electronics GmbH
1
2
3
Figure 59: Data Point Manager Dialog
7.2.1 Folder List
At the left is a list of folders which is used to sort the available data objects by their
category. There are a number of predefined folders available:
•
Imported
: This folder has a number of sub-folders for different import methods:
o
CEA709 CSV Import:
This folder is used to display data points imported
from CSV files.
o
CEA709 LNS Database Scan
: This folder is used to hold data retrieved from
a network database scan.
o
CEA709 Network Scan
: This folder holds NVs scanned online from an
attached CEA-709 network. For each CEA709 port of the device, there is a
separate scan folder.
Data objects in the import folder are not stored on the device when the project is
downloaded. They represent data objects which are available on remote devices
and are shown here as templates to create suitable data objects for use on the
device by selecting the
Use on Device
option.
•
CEA709 Templates
: This folder contains the created data point templates. They
contain a set of properties, which are applied to CEA-709 data points, when they are
created on the L-Proxy.
•
L-Proxy
: This is the device folder of the L-Proxy. It contains all the necessary data
points which constitute to the L-Proxy’s port interface definition. These data points are
created on the L-Proxy when the configuration is downloaded. The three subfolders
represent
o
System Registers
: This folder contains system registers, which provide
information on the device itself.
o
User Registers
: This folder holds user-definable registers. These registers are
not visible on the underlying network and are intended for internal usage.
o
CEA-709 Port
: This folder contains local data points, and remote data points
of the CEA-709 network technology. For each CEA709 port of the device,
there is a separate scan folder.