L-Proxy User Manual
72
LOYTEC
Version 3.1
LOYTEC electronics GmbH
Figure 61: Data Point Naming Rules Project Settings.
7.3.3 CEA-709 Settings
The CEA-709 configuration tab as shown in Figure 62 allows configuring properties of the
device’s CEA-709 port. The options are:
•
Enable Legacy Network Management Mode
: This group box contains check boxes
for each CEA-709 port of the device. Put a check mark on the port, if this port shall be
operated in the legacy network management mode. In that mode, the port does not use
the extended command set (ECS) of network management commands. This can be
necessary to operate the device with some network management tools that do not
support the ECS.
•
Default Pollcycle for External NVs
: When using external NVs, this pollcycle is set as
a default for input data points. The pollcycle can be edited individually in the
properties view of the data point manager.
•
Use state-member of SNVT_switch as
: This setting defines how the state member of
the SNVT_switch shall be mapped to a data point. Depending on how the data point
shall be used, it can be binary or multi-state. The multi-state setting allows setting the
UNSET state explicitly. As a binary point the UNSET state is implicitly chosen, if the
value is invalid.
•
L-Proxy Operating Mode
: The L-Proxy Configurator can be operated in one of two
modes: Simple and advanced mode. In simple mode, the user can only use dynamic
NVs created manually in LNS and create connections. The LNS database is never
modified in this mode. In advanced mode, the user has full command over static,
dynamic, and external NVs, automatic bindings and connections. The default mode is
the simple mode.