3.4.3 FT Activity LED
The FT port on the L-Proxy has a three-color LED (green, red, and orange, see Figure 6).
Table 1 shows different LED patterns of the port and their meaning.
Behavior
Description
Comment
GREEN flashing fast
Traffic
GREEN flashing at 1Hz
The L-Proxy’s port is unconfigured
RED permanent
Port damaged
RED flashing fast
Traffic with high amount of errors
RED flashing at 1 Hz
(all ports)
Firmware image corrupt
Please upload new firmware.
ORANGE permanent
Port disabled
e.g., using LSD Tool
ORANGE flashing fast
Traffic on port configured as management port
e.g., using LSD Tool
Table 1: CEA-709 Activity LED Patterns
3.4.4 Ethernet Link LED
The Ethernet Link LED lights up green whenever an Ethernet cable is plugged-in and a
physical connection with a switch, hub, or PC can be established.
3.4.5 Ethernet Activity LED
The Ethernet Activity LED lights up green for 6 ms whenever a packet is transmitted or
received or when a collision is detected on the network cable.
3.4.6 CNIP LED
The CNIP LED is a three color LED that indicates different operating states of the
L-Proxy’s CEA-852 device.
Green: The CEA-852 device is fully functional and all CEA-852 configuration data
(channel routing info, channel membership list, send list) are up-to-date.
Green flicker: If a valid CEA-709 packet is received or transmitted over the IP channel the
CNIP LED turns off for 50 ms. Only valid CEA-709 IP packets sent to the IP address of
the L-Proxy can be seen. Stale packets or packets not addressed to the L-Proxy are not
seen.
Yellow: Device is functional but some configuration data is not up-to-date (device cannot
contact configuration server but has configuration data saved in Flash memory)
Red: Device is non-functional because it was rejected from the CEA-852 IP channel or
shut-down itself due to an internal error condition.
Off: Device is non-functional because the CEA-852 device has not started. This can be the
case if the L-Proxy uses DHCP and it has not received a valid IP configuration (address)
from the DHCP server.
Flashing red at 1 Hz: Device is non-functional because the CEA-852 device is started but
has not been configured. Please add the device to a CEA-852 IP channel (register in
configuration server).
Flashing green or orange at 1 Hz: The L-Proxy’s CEA-709 side of the gateway has not
been commissioned yet. The color indicates the CEA-852 IP channel status as described
above.