H100 _
49
Energy Saving Drive
Motor 2 (2nd Motor) Function Group (M2)
1
Code Comm. No.
Name
LCD Display
Set Range
Default
Attribute
*
00
-
Jump Code
Jump Code
1~99
14
O
04
0h1E04
Acceleration time
M2-Acc Time
20.0
0.75~90kW
-
O
60.0
110~250kW
100.0
315~500kW
05
0h1E05
Deceleration time
M2-Dec Time
30.0
0.75~90kW
-
O
90.0
110~250kW
150.0
315~500kW
06
0h1E06
Motor capacity
M2-Capacity
0
0.2kW(0.3HP)
-
Δ
1
0.4kW(0.5HP)
2
0.75kW(1.0HP)
3
1.1kW(1.5HP)
4
1.5kW(2.0HP)
5
2.2kW(3.0HP)
6
3.0kW(4.0HP)
7
3.7 kW(5.0HP)
8
4.0 kW(5.5HP)
9
5.5 kW(7.5HP)
10
7.5 kW(10.0HP)
11
11.0 kW(15.0HP)
12
15.0 kW(20.0HP)
13
18.5 kW(25.0HP)
14
22.0 kW(30.0HP)
15
30.0 kW(40.0HP)
16
37.0 kW(50.0HP)
17
45.0 kW(60.0HP)
18
55.0 kW(75.0HP)
19
75.0 kW(100.0HP)
20
90.0 kW(125.0HP)
21
110.0 kW(150.0HP)
22
132.0 kW(200.0HP)
23
160.0 kW(250.0HP)
24
185.0 kW(300.0HP)
25
220.0 kW(350.0HP)
26
250.0 kW(400.0HP)
27
315.0 kW(500.0HP)
28
355.0 kW(550.0HP)
29
400.0 kW(650.0HP)
30
500.0 kW(800.0HP)
07
0h1E07
Base frequency
M2-Base Freq
30.00~400.00(Hz)
60.00
Δ
08
0h1E08
Control mode
M2-Ctrl Mode
0
V/F
0:V/F
Δ
2
Slip Compen
10
0h1E0A
Number of motor poles
M2-Pole Num
2~48
Varies according to the
motor type
Δ
11
0h1E0B
Rated slip speed
M2-Rated Slip
0~3000(Rpm)
12
0h1E0C
Motor: rated current
M2-Rated Curr
1.0~1000.0(A)
13
0h1E0D
Motor: no load current
M2-Noload Curr
0.0~1000.0(A)
14
0h1E0E
Motor: rated voltage
M2-Rated Volt
0
2
, 170~480(V)
15
0h1E0F
Motor efficiency
M2-Efficiency
70~100(%)
17
-
Stator resistance
M2-Rs
0.000~9.999(Ω)
18
0h1E12
Leakage inductance
M2-Lsigma
0.00~99.99(mH)
25
0h1E19
V/F pattern
M2-V/F Patt
0
Linear
0: Linear
Δ
1
Square
2
User V/F
26
0h1E1A
Forward torque boost
M2-Fwd Boost
0.0~15.0(%)
2.0
0.75~90kW
Δ
0.0~15.0(%)
1.0
110~500kW
27
0h1E1B
Reverse torque boost
M2-Rev Boost
0.0~15.0(%)
2.0
0.75~90kW
Δ
0.0~15.0(%)
1.0
110~500kW
28
0h1E1C
Stall prevention level
M2-Stall Lev
30~150(%)
130
Δ
29
0h1E1D
Overheat prevention: 1 min rating
M2-ETH 1min
100~150(%)
120
Δ
30
0h1C1E
Overheat prevention: continuous rating
M2-ETH Cont
50~120(%)
100
Δ
1
Motor 2 Function Group appears when one ofI N-65~71 codes is set as 26(2nd MOTOR).
2
Refer to the 4.15-motor output voltage adjustment