3.1 General Standards
General specifications of XGT Panel are as follows.
No.
Item
standard
Related
Standards
1
Ambient
temperature
0 ° C ~ + 50 ° C
-
2
Storage temperature
-20 ° C ~ + 60 ° C
-
3
Operating humidity
10
∼
85%RH, non-condensing.
-
4
Storage humidity
10
∼
85%RH, non-condensing.
-
5
Vibration
resistance
Occasional vibration
Count
-
frequency
acceleration
amplitude
10 times each
in X, Y and Z
direction
IEC 61131-2
5≤f<9 Hz
-
3.5mm
9≤f≤150 Hz
9.8m/s
2
-
Continuous vibration
frequency
acceleration
amplitude
5≤f< 9 Hz
-
1.75mm
9≤f≤150 Hz
4.9m/s
2
-
6
Shock endurance
* Maximum shock acceleration: 147m/s
2
(15G)
* Duration time: 11ms
* Pulse wave: half sine pulse (3 times each in X, Y and Z directions)
IEC 61131-2
7
Noise
Immunity
Square wave
Impulse noise
AC: ± 1,500V
DC: ± 1,000V
LS
ELECTRIC
Electrostatic
Discharge
Immunity
± 4 kV (contact discharge), ± 8 kV (air discharge)
IEC 61131-2
IEC 61000-4-2
Electromagnetic
Radiated
Emissions
80 ~ 1,000 MHz, 10 V / m
IEC 61131-2
IEC 61000-4-3
Fast
Transient
/ Burst noise
Category
Power module
Communication interface
IEC 61131-2
IEC 61000-4-4
Voltage
2 kV
1 kV
Surge
Category
AC power
DC power supply
Communication
interface
IEC 61131-2
Voltage
2kV (LG)
1 kV (LL)
1kV (LG)
0.5 kV (LL)
1 kV
8
Environment
Free from corrosive gases and excessive dust
-
9
Operating height
Below 2,000m (6,562ft)
-
10
Pollution degree
2 or less
-
11
Cooling method
Natural Air-Cooling
-
Summary of Contents for iXP2 Series
Page 1: ...Human Machine Interface XGT PANEL iXP2 Series ...
Page 51: ...Chapter 5 XGT Panel Menu Explanation 5 14 ...
Page 127: ...Appendix2 Dimensions APP2 1 Appendix 2 Dimensions Unit mm 1 iXP2 08xxA D ...
Page 128: ...Appendix2 Dimensions APP2 2 2 iXP2 10xxA D ...
Page 129: ...Appendix2 Dimensions APP2 3 3 iXP2 12xxA D ...