Chapter 3 Standard Specification
3-4
(2) Special Type
Item
iXP2-08xxA/D-EX
iXP2-10xxA/D-EX
iXP2-12xxA/D-EX
iXP2-15xxA/D-EX
Display type
TFT color LCD
Screen size
8.4 "
10.4 "
12.1 "
15 "
Display resolution
800 x 600
1024 x 768
Color indication
24-bit color (16.7M colors)
Indication degree
Right and left: 80 deg.
Top: 80 deg.
Bottom: 60 deg.
Right: 75 deg.
Top: 75 deg.
Bottom: 75 deg.
Right and left: 80 deg.
Top: 80 deg.
Bottom: 80 deg.
Backlight
LED method, automatic On / Off support
Backlight lifetime
50,000 hour
Touch panel
Capacitive Touch
Audio otput
Magnetic Buzzer (85dB)
Processor
1GHz, Dual core
Memory
Flash
1GB
Operating RAM
1GB
Backup RAM
1 Mbyte
Backup data
Date / Time data, Logging / Alarm / Recipe data, Non-volatile devices
Battery
CR2032(3.0V/210mAh, About 3years/25
℃
)
Video Output
1 x HDMI
Audio Out
3.5Ф x 1, 40mW
Ethernet
1 x 10Base-T / 100Base-TX, 1 x 10Base-T / 100Base-TX / 1000Base-T
USB host
3 x USB 2.0 (Front x 1, Rear x 2)
USB device
1 x USB 2.0 (Send / Receive front, PC and project data etc.)
RS-232C
1 x RS-232C (DSUB 9 / Male type)
RS-422/485
1 x RS-422/485 (Terminal Block)
Multi-language
Can display 12 languages simultaneously
Animation
GIF format support
Recipe
Support
Data logging
Support
Script Launcher
Support
Standard Certification
CE, KC, UL, IECEx, ATEX, KCs
Protection standard
Ex nA IIC T5 Gc, Ex tc IIIC T100
℃
Dc IP64
Dimensions (mm)
240 × 180 × 60
271 x 212 x 60
313 × 239 × 60
395 × 294 × 66
Panel Cut (mm)
228.5 x 158.5
259.0 x 201.0
301.5 x 227.5
383.5 x 282.5
Power
A(AC100~240V), D(DC19.2~28.8V)
Power consumption (W)
25
25
30
30
Weight (Kg)
1.87
2.35
3.0
4.6
Specific conditions
of use
1. The equipment presents a potential electrostatic hazard. Clean only with a damp cloth.
2. The device for nA marked equipment shall be installed in an enclosure that maintains and ingress protection rating of at least IP4X
where there are bare live parts and the equipment is intended for installation only in locations proving adequate protection against the
entry of solid foreign objects or water capable of impairing safety.
The device for tc marked equipment shall be installed in an enclosure IP64 in accordance with IEC 60079-31.
3. Must be installed in accordance with EN 60079-14.
4. Do not connect or separate plugs and sockets while an explosive atmosphere is present.
Summary of Contents for iXP2 Series
Page 1: ...Human Machine Interface XGT PANEL iXP2 Series ...
Page 51: ...Chapter 5 XGT Panel Menu Explanation 5 14 ...
Page 127: ...Appendix2 Dimensions APP2 1 Appendix 2 Dimensions Unit mm 1 iXP2 08xxA D ...
Page 128: ...Appendix2 Dimensions APP2 2 2 iXP2 10xxA D ...
Page 129: ...Appendix2 Dimensions APP2 3 3 iXP2 12xxA D ...