Chapter 4. Installation and Wiring
4-1
Chapter 4 Installation and Wiring
4.1 Installation
4.1.1
Installation environment
This machine has high reliability regardless environment. But for reliability and stability, be careful the followings
(1) Environment condition
(a) Install at the panel which can protect this machine from water and dust. XGT Panel is designed by IP66
Standard in front parts and IP20 Standard in rear parts.
(b) Install at the place where impact and vibration is not continuously applied. XGT Panel is designed to
meet IEC standard (IEC 61131-2).
(c) Do not expose this machine to direct light.
(d) Do not install at the place where rapid temperature change can occur. Moisture by rapid temperature
change can cause malfunction and damage.
(e) If the XGT Panel is exposed to low or severe temperature changes, dew may may occur between
the front panel and LCD screen. In this case, malfunction or damage of the product may occur, so wait until
the surface temperature of the XGT Panel is close to the ambient temperature before turning on the power.
(f) This machine should be installed within 0~50°C, otherwise the screen may be changed or cause
malfunction.
(g) This machine should be installed within 10~85% relative-humidity. Moisture by rapid temperature change
can cause malfunction and damage.
(h) Avoid corrosive gas and burnable gas.
(2) Installation construction
(a) When doing screw’s processing or wiring construction, be careful that the remains do not enter the XGT
Panel inside.
(b) Install at the place where you can easily control.
(c) Do not install with high voltage machine within same Panel.
(d) Keep distance of more than 100mm from duct for wiring and peripheral machine.
(e) Ground at the place where few noises develop.
(3) Anti-heat design of control panel
(a) In case of installing XGT Panel in the airtight panel, consider the heat by other machine as well as own
heat. In case that the air circulates through a ventilating opening or a general pan, XGT Panel system can
be influenced by in-draft of dust or gas.
(b) We recommend you to install a filter or to use an airtight heat exchanger.
Summary of Contents for iXP2 Series
Page 1: ...Human Machine Interface XGT PANEL iXP2 Series ...
Page 51: ...Chapter 5 XGT Panel Menu Explanation 5 14 ...
Page 127: ...Appendix2 Dimensions APP2 1 Appendix 2 Dimensions Unit mm 1 iXP2 08xxA D ...
Page 128: ...Appendix2 Dimensions APP2 2 2 iXP2 10xxA D ...
Page 129: ...Appendix2 Dimensions APP2 3 3 iXP2 12xxA D ...