![background image](http://html1.mh-extra.com/html/ls-industrial-systems/starvert-ig5a/starvert-ig5a_manual_1943844021.webp)
Compact & Powerful Inverter iG5A
21
Function List
LED Parameter
Description
Factory Adj.
during
display
name
default
run
LED Parameter
Description
Factory Adj.
during
display
name
default
run
Drive Group
0.00
ACC
dEC
drv
Frq
St1
St2
St3
CUr
rPM
dCL
vOL
nOn
drC
Drv2
Frq2
During stop: Frequency command
During run: Output frequency
Accel time
Decel time
Drive mode
Frequency setting method
Multi-Step frequency 1
Multi-Step frequency 2
Multi-Step frequency 3
Output current
Motor RPM
Inverter DC link voltage
User display select
Fault display
Direction of motor rotation select
Drive mode 2
Frequency setting method 2
0~400Hz
0~6000sec
0 (Keypad), 1 (FX/RX-1), 2 (FX/RX-2), 3 (RS-485)
0 (Keypad-1), 1 (Keypad-2), 2 (V1S: -10~10V), 3 (V1: 0~10V)
4 (I: 0~20mA), 5 (V1S+1), 6 (V1+I), 7 (RS-485)
0~400Hz
A
rpm
V
vOL, Por, tOr
-
F (Forward), R (Reverse)
0 (Keypad), 1 (FX/RX-1), 2 (FX/RX-2)
0 (Keypad-1), 1 (Keypad-2), 2 (V1S-: 10~10V), 3 (V: 0~10V)
4 (I: 0~20mA), 5 (V1S+I), 6 (V1+I)
0.00
5.0
10.0
1
0
10.00
20.00
30.00
–
–
–
vOL
nOn
F
1
0
Yes
Yes
Yes
No
No
Yes
Yes
Yes
–
–
–
–
–
Yes
No
No
Function group 1
F0
F1
F2
F3
F4
F8
F9
F10
F11
F12
F13
F14
F20
F21
F22
F23
F24
F25
F26
Jump code
Forward/Reverse run disable
Accel pattern
Decel pattern
Stop mode select
DC brake start frequency
DC brake wait time
DC brake voltage
DC brake time
DC brake start voltage
DC brake start time
Time for magnetizing a motor
Jog frequency
Max. frequency
Base frequency
Start frequency
Frequency high/low limit select
Frequency high limit
Frequency low limit
0~60
0 (Fwd and rev run enable), 1 (Forward run disable), 2 (Reverse run disable)
0 (Linear), 1 (S-curve)
0 (Decelerate to stop), 1 (DC brake to stop), 2 (Free run to stop)
Start frequency, 0~60Hz
0~60sec
0~200%
0~60sec
0~200%
0~60sec
0~60sec
0~400Hz
40~400Hz
30~400Hz
0~10Hz
0 (NO),1 (YES)
0~400Hz
0.1~400Hz
1
0
0
0
0
5.00
0.1
50
1.0
50
0
1.0
10.00
60.00
60.00
0.50
0 (No)
60.00
0.50
Yes
No
No
No
No
No
No
No
No
No
No
Yes
No
No
No
No
No
No
1)
1) Only displayed when F4 is set to 1 (DC brake to stop).
2) If H40 is set to 3 (Sensorless vector), Max. frequency is settable up to 300Hz.
3) Only displayed when F24 (Frequency high/low limit select) is set to 1.
1) Only displayed when one of the multi-function input terminals 1-8 [
I
17~
I
24] is set to “22”.
1)
2)
3)
Summary of Contents for STARVERT iG5A