![background image](http://html.mh-extra.com/html/ls-industrial-systems/sv-ie5-series/sv-ie5-series_user-manual_1943834039.webp)
Chapter 7. Function List
7-3
z
PG Group
Display Name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
Page
P 0
Jump code
0 ~ 88
Sets the code number to jump
1
O
5-5
P 1
Fault log 1
-
It logs the information on the types of
faults, and the frequency, current and
status such as acceleration, deceleration
and stop at the time of trouble. The latest
fault is automatically recorded in log 1.
nOn -
P 2
Fault log 2
-
nOn
-
P 3
Fault log 3
-
nOn
-
P 4
Fault log removal 0 ~ 1
Remove log P1~P3.
0
O
11-4
0
Both F/R directions available
1
Forward rotation prohibited
P 5
Prohibition
of
forward/reverse
rotation
0 ~ 2
2 Reverse
rotation
prohibited
0 X
9-7
P 6
Acc pattern
0
Linear pattern operation
P 7
Dec pattern
0 ~ 1
1 S-curve
pattern
operation
0 X
9-9
0
Deceleration to stop
1
DC brake to stop
P 8
Stop
mode
selection
0 ~ 2
2
Free run to stop
0 X
9-14
P 9
1)
DC brake start
frequency
0.1 ~ 60
[Hz]
It sets DC brake start frequency.
It cannot be set below start
frequency(P18).
5.00 X
P10
DC brake wait
time
0 ~ 60
[sec]
When DC brake frequency is reached,
the inverter holds the output for the
setting time before starting DC brake.
0.10 X
P11
DC brake voltage
amount
0 ~ 200
[%]
It sets the amount of DC voltage applied
to a motor. Motor rated current(P43).
50 X
P12
DC brake time
0 ~ 60
[sec]
It sets the time taken to apply DC current
to a motor.
1.0 X
10-1
1)
Displayed only when P8 is set to 1(DC brake to stop)