Chapter 9. Basic Functions
9-15
9.7
Frequency limit
z
Frequency limit using Max Frequency and Start Frequency
Group
Code Parameter Name
Setting
Range
Initial
Unit
P16
Max frequency
-
0 ~ 200
60.0
Hz
PG Group
P18
Start frequency
-
0.1 ~ 10
0.5
Hz
Max Frequency: Every frequency except P17(base frequency) has upper limit of frequency parameter.
Therefore, any frequency cannot be set above the max. frequency.
Start Frequency: Every frequency has lower limit of frequency parameter.. If a frequency is set lower than
this, 0.00 is automatically set.
Max frequency is the reference frequency serving as the criteria of accel/decel time as well as upper limit.
Once max. frequency is changed, accel/decel slope may be changed accordingly.
FX
Frequency
Accel time
Decel time
Max
frequency
Time