Chapter 10. Advanced Functions
10-3
Voltage
Operation
command
P13
P3
10.2
Jog
operation
Group
Code Parameter Name
Setting
Range
Initial
Unit
PG Group
P15
Jog frequency
-
0 ~ 200
10.0
Hz
PG Group
P68
Multi-function input terminal P3 select
4
0 ~ 24
2
Set a desirable jog frequency in P15 of PG Group.
Select a terminal from P1 – P5 to use for this setting
If P3 is set for Jog operation, set P68 to 4(Jog operation).
Jog frequency can be set within Max frequency(P16) and Start frequency(P18).
Jog operation overrides all other operations except Dwell operation. Therefore, if Jog frequency command
is entered in the middle of Multi-Step, Up-Down or 3-wire operation, operation is executed at Jog frequency.
The above diagram shows an example when Multi-function input is set to NPN mode.
P3 (JOG)
Operation
command(FX)
Frequency
P15
P1
P3
CM
FX : P66=0
JOG : P68=4