Chapter 6 Instruction Details
XBC E-Type Main Unit
6-67
Ver. 1
6.17.2 TON
Instruction
Area Available
Step
Flag
P M K F L T C S Z D.x R.x
Co
nst.
U N D R
Error
(F110)
Zero
(F111)
Carry
(F112)
TON
T
-
-
-
-
- O -
-
-
-
-
-
-
-
-
-
2/3
-
-
-
t
O O O -
-
-
-
-
-
-
- O O - O O
Operand
Description
Data Type
T
Timer Contact to use
WORD
t
stands for Timer’s setting value. Integer or word device available
Setting Time = Basic cycle (100ms, 10ms, 1ms) x setting value (t)
WORD
1) TON (On Timer)
(1) The moment input condition is On, present value increases and Timer Contact will be On if set time (t) is
reached.
(2) If input condition is Off or meets Reset Instruction, Timer Output is Off, and present value is “0”.
2) Program Example
(1) In 20 sec after P00020 is On, when Timer’s present value is the same as set value, T0097 will be On, and
P00065 is On.
(2) If input condition is Off before present value reaches set value, present value will be “0”. If P00021 is On,
T0097 will be Off and present value “0”.
[Ladder Program]
[Mnemonic Program]
TON
Input Condition
TON
T
t
Step Mnemonic
Operand
0
LOAD
1
TON
P00020
T0097 200
3
LOAD
4
OUT
5
LOAD
6
RST
T0097
T0097
P00021
P00065
P00020
0
3
5
P00021
TON T0097 200
T0097
P00065
R
T0097
←
→
t
(Increased)
Input signal
Timer contact
point output