![background image](http://html1.mh-extra.com/html/ls-industrial-systems/xbc-dn10e/xbc-dn10e_user-manual_1943831210.webp)
Chapter 6 Instruction Details
XBC E-Type Main Unit
6-93
Ver. 1
6.19.4 GMOV, GMOVP
Instruction
Area Available
Step
Flag
P M K F L T C S Z D.x R.x
Co
nst.
U N D R
Error
(F110)
Zero
(F111)
Carry
(F112)
GMOV(P)
S O O O O O O O - O -
- O O O O O
4~6
O
-
-
D O O O - O O O - O -
-
- O O O O
N O O O - O -
-
- O -
- O O O O O
Operand
Description
Data Size
S
Data to transfer or device number data is saved in
WORD
D
Device number to save data transferred
WORD
N
Number to transfer in group (0 ~ 65536)
WORD
[Flag Set]
Flag
Description
Device Number
Error
If N’s range exceeds specified area. Applicable instruction result is not
processed.
F110
1) GMOV (Group Move)
(1) Transfers N word data from S to D.
(2) MOV Instruction transfers word 1: 1, and GMOV Instruction transfers word N: N.
2) Program Example
(1) If Input Signal P00020 is On, D00000, D00001, and D00002 word data is saved in P00004, P00005, and
P00006.
GMOV D00000 P0004 3
P00020
GMOV
GMOVP
S
D
GMOVP
GMOV
S
D
N
N
N
P00004
h0001
h0004
h005F
D00000
S(Source)
GMOV
Execute
D(Destination)
(Before)
(After)
D00002
D00001
P00006
P00005
h0001
h0004
h005F
h0002
h0007
h007F
h005A
S
S+1
.
.
.
S+N-1
Word value
h0002
h0007
h007F
h005A
D
D+1
.
.
.
D+N
- 1
Group
transfortation
N
N
Summary of Contents for XBC-DN10E