![background image](http://html1.mh-extra.com/html/ls-industrial-systems/xbc-dn10e/xbc-dn10e_user-manual_1943831211.webp)
Chapter 6 Instruction Details
XBC E-Type Main Unit
6-94
Ver. 1
6.19.5 FMOV, FMOVP
Instruction
Area Available
Step
Flag
P M K F L T C S Z D.x R.x
Co
nst.
U N D R
Error
(F110)
Zero
(F111)
Carry
(F112)
FMOV(P)
S O O O O O O O - O -
- O O O O O
4~6
O
-
-
D O O O - O O O
O -
-
- O O O O
N O O O - O -
-
- O -
- O O O O O
Operand
Description
Data Size
S
Data to transfer or device number data is saved in
WORD
D
Device number to save data transferred
WORD
N
Number to transfer in group (0 ~ 65,536)
WORD
[Flag Set]
Flag
Description
Device Number
Error
If Z’s range exceeds specified area. Applicable instruction result is not
processed.
F110
1) FMOV (File Move)
(1) Transfers Word data S for N Word from D in regular order.
(2) Mainly used to initialize data’s specific area.
(3) N’s range exceeds specified area, Error Flag (F110) will be set but not processed.
2) Program Example
Whenever Input Signal P00020 is On, D00002 word data is saved in P0004, P0005, P0006.
FMOVP D00002 P0004 3
P00020
FMOVP execution
D00002
P0004
P0005
P0006
h0098
h0098
h0098
h0098
Word
Value
FMOV
FMOVP
S
D
FMOVP
FMOV
S
D
N
N
S1(Source) FMOV execution
(Destination)
Word
value
D00000
M00000
(After)
N=4
M00003
M00001
M00002
h0052
h0052
h0052
h0052
h0052
D
FMOV D00000 M0000 4
P00020