Chapter 6 Instruction Details
XBC E-Type Main Unit
6-199
Ver. 1
6.31 Display Instruction
6.31.1 SEG, SEGP
Instruction
Area Available
Step
Flag
P M K F L T C S Z D.x R.x
Co
nst.
U N D R
Error
(F110)
Zero
(F111)
Carry
(F112)
SEG(P)
S O O O O - O O - O -
- O O O O O
4
O
-
-
D O O O -
- O O - O -
-
- O O O O
Z O O O -
-
-
-
- O -
- O O O O O
Operand
Description
Data Type
S
Address where data to decode in 7 segments is saved.
BIN 32
D
Address to save data decoded.
BIN 32
Z
Format to display
BIN 16
[Flag Set]
Flag
Description
Device
Number
Error
To be set if Z’s format regulation is incorrect.
F110
1) SEG (7 Segments)
(1) Saves 7 segments of N digits decoded from S by Z’s specified format in D.
Z’s format (Hexadecimal)
D’s Start bit
S’s Start bit
Don’t care
Number
conveted(0~4)
Sst
Dst
Dnt
n
(2) Where ‘n’ means the number of digits to be converted in 4-bit unit.
(3) If ‘n’ is 0, there will be no conversion.
b15
b0
S
0
0
0
0
0
0
0
0
0
1
1
0
0
1
1
1
b15
b0
D
0
1
1
1
1
1
0
1
0
0
1
0
0
1
1
1
n = 2
n = 1
SEG
SEGP
S
D
means
SEG
Z
S
D
Z
P