Chapter 3 Installation and Wiring
XBC E-Type Main Unit
3-16
Ver. 1
3.6.1 Wiring General Specifications
1. Do not use a ferrule with the XGB terminal strip. Ring and Fork terminals or stranded wire are
acceptable.
2. Terminal strip torque should be 42 - 58 N/cm (3.7 – 5.1 in/lb).
3.6.2 On-Board Power Supply
1. Power supply specification of main unit.
Items
Specification
XBC-Dx10/14E
XBC-Dx20/30E
Input
Rated voltage
(UL warranty voltage)
AC 100 ~ 240 V
Input voltage range
AC85~264V(-15%, +10%)
Inrush current
50A
Peak
or less
Input current
0.5A or less (220V), 1A or less (110V)
Efficiency
65%
Permitted momentary
power failure
10ms or less
Output
Rated
output
DC5V
500mA
800mA
DC24V
0.2A
0.2A
Output voltage ripple
DC5V (
±
2%)
Power supply status indication
LED On when power supply is normal
Cable specification
0.75 ~ 2 mm
2
Types of external
connection
Cable specification mm
2
(AWG)
Minimum
Maximum
Digital input
0.18 (AWG24)
1.5 (AWG16)
Digital output
0.18 (AWG24)
2.0 (AWG14)
Analogue I/O
0.18 (AWG24)
1.5 (AWG16)
Communication
0.18 (AWG24)
1.5 (AWG16)
Main power
1.5 (AWG16)
2.5 (AWG12)
Protective grounding
1.5 (AWG16)
2.5 (AWG12)