Chapter 7 Built-in High-speed Counter Function
XBC E-Type Main Unit
7-21
Ver. 1
8. Preset function
It changes the current value into preset value. There are two types of preset function, internal
preset and external preset. External preset is fixed as input contact point.
a. Preset setting value is saved at the following special K area.
Type
Area per each channel (Double word)
Ref.
Ch.0
Ch.1
Ch.2
Ch.3
Internal preset
K304
K334
K364
K394
-
External preset
K306
K336
K366
K396
-
b. Preset command is specified through the following special K area, external preset is
used by executing the designated input contact point after allowance bit is on.
Type
Area per each channel (Bit)
Ref.
Ch.0
Ch.1
Ch.2
Ch.3
Internal preset
command
K2601
K2701
K2801
K2901
-
External preset
allowance
K2602
K2702
K2802
K2902
-
External preset
command
P004
P005
P006
P007
-