Chapter 10 Maintenance
XBC E-Type Main Unit
10-13
Ver. 1
The load does
not turn off.
Leakage current due to the use of two different
power supplies.
Use only one power supply.
Connect a blocking diode.
If the load is inductive (i.e. relay, contactor,
solenoid, transformer, etc.), install a diode to
clamp the back EMF.
Output
Load
E
E
E1
Load
E2
Output