Industrial Drive for Fan and Pump
STARVERT iP5A
Sink mode (NPN mode)
•
Put J1 switch down to set to Sink mode
(NPN mode). CM terminal (24V GND) is
common terminal for contact signal
input.
•
The factory default is Sink mode
(NPN mode).
Source mode (PNP mode)
Internal Power Supply Used
•
Put J1 switch up to set to Source mode
(PNP mode). Terminal 24 (24V Power
Supply) is common terminal for contact
input signal.
Source mode (PNP mode)
External Power Supply Used
•
Put J1 switch up to set to Source mode
(PNP mode).
•
To use external 24V Power Supply,
make a sequence between external
Power Supply (-) terminal and CM
(24V GND) terminal.
iP5A provides Sink/Source (NPN/PNP) modes for sequence input terminal on the control circuit. The logic of the
input terminal is settable to Sink mode (NPN mode)/Source mode (NPN mode) by using the J1 switch.
Connection method is shown below.
M1, M2, M3
Programmable
Digital Input 1, 2, 3
FX [M7]
Forward Run
Command
RX [M8]
Reverse Run
Command
JOG [M6]
Jog Frequency
Starting
Reference
Contact
Function
BX [M5]
Emergency Stop
Select
RST [M4]
Fault Reset
CM
Sequence Common
(NPN)
24
Sequence Common
(PNP)
V+, V-
Analog Power Source
(+12V,-12V)
V1
Frequency Reference
(Voltage)
Analog
I
Frequency Reference
Frequency
(Current)
Setting
A0, B0
Frequency Reference
(Pulse)
5G (~30kW)
Frequency Reference
CM (37kW~)
Common Terminal
External
NT (~30kW)
External Motor
Motor Thermal
ET (37kW~)
Thermal Detection
Detection
5G
Common for
NT (or ET)
C+, C-
RS485 signal
High,
Low
CM
RS485 common
Programmable
Analog Output
S0, S1,
Voltage Output
5G
Analog Common Terminal
Fault Contact
3A, 3C, 3B
Output
Contact
A1~4, C1~4
Programmable
Digital
Output
21
Drive Starvert iP5A Series