Relay Terminal No.
Contact Output Description
3
Normally
Open
4
Common
5
Normally
Closed
The lockout solenoids on cranes are normally energised when crane is in safe
condition (no alarm) and are de-energised when a motion cut condition occurs.
Use contact terminals 4 (com) and 5 (NC) of the motion cut relay to wire the
supply coil of the lockout solenoids. During motion cut activation, the motion cut
relay is de-energised. This opens the relay contacts and also de-energises the
lockout solenoids.
The Switchbox has a spare gland for motion cut cable entry. Please note that
the motion cut cable is not supplied with the RCI-1502 System as a standard
component.
Drawing Reference:
DWG 3336 – “RCI-1502 Switchbox V2 Wiring Diagram”
Summary of Contents for RCI-1502 LM
Page 2: ......
Page 53: ...Appendix 8 1 Data Logging on RCI Systems ...
Page 54: ......
Page 60: ...Data Logging on RCI Systems Example Lift Cycles ...
Page 65: ...Appendix 8 2 Drawings ...
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 71: ...U N C O N T R O L L E D C O P Y ...
Page 72: ...APPROVED BY TOL 0 0 0 1 2 3 4 55 26 2 0 7 2 8 9 1 1 1 1 0 7 5 6 2 ...
Page 73: ......
Page 74: ...APPROVED BY TOL 0 0 0 1 22 3 4 5 6 0 22 2 1 7 8 98 1 7 8 98 7 8 98 7 8 98 1 0 9 8 3 6 8 3 ...
Page 75: ......
Page 76: ... APPROVED BY 0 1 2 22 3 3 3 TOL 4 4 23 4 232 22 3 242 4 2 32 2 3516 7 8 7 7 9 2 3 42 4 2 ...
Page 77: ......
Page 78: ... APPROVED BY 0 1 2 22 3 3 3 TOL 4 4 23 4 232 22 5 0 42 4 2 3617 8 9 8 8 2 ...
Page 79: ......
Page 80: ......
Page 84: ......
Page 85: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......