configure the master instrument using both its measures (marked with symbol
)
and the serial measures (marked with symbol
) coming from slave instrument; the
serial measurements coming from slave instrument can be imported directly from
Import
function in 3DOM software selecting the correct configuration to be
imported;
check the agreement between the measures acquired from slave and the serial
measures received from master (most of all the values of
Sensor’s Protocol Address
and
Index of measure in the sensor
); the uncorrect agreement prevent the master
instrument from acquiring correctly;
for M-Log master configure in serial communication parameters of port 2:
Protocol
Type
=Native and
Velocity
=57600;
for M-Log slave configure in serial communication parameters of port 2:
Network
Address
=1,
Spontaneous transmission Rate
≠0 (input one rate lower than the
acquisition rate of fast serial measure set up on master; we recommend the input of
slave’s transmission rate half of master’s acquisition rate) and Message transmission
repetitions ≥1; see the following example:
for serial measures, that have to be received from master instrument, set up the
Sensor’s Protocol Address
equal
Instrument’s Network Address
selected for serial
communication port 2 of slave instrument; recommended default value is 1.
So it’ll be possible the remote modification (through 3DOM software ) of instrument’s
configuration, but it won’t be possible the remote modification of slave’s configuration