7. Function List
7-13
LED
display
Parameter
Name
Min/Max
Range
Description
Factory
defaults
Adjustable
during run
Page
H51
[P gain for
PID
controller]
0/999.9
[%]
This parameter sets
the gains for the PID
controller.
300.0
O
H52
[Integral
time for PID
controller
(I gain)]
0.1/32.0
[sec]
1.0
O
H53
Differential
time for PID
controller
(D gain)
0.0 /30.0
[sec]
0.0
O
H54
F gain for
PID
controller
0/999.9
[%]
This is the Feed
forward gain for the PID
controller.
0.0
O
H55
[PID output
frequency
limit]
0/400
[Hz]
This parameter limits
the amount of the output
frequency thru the PID
control.
The value is settable
within the range of F21
– [Max frequency] and
H23 – [Start frequency].
60.0
O
H70
[Frequency
Reference
for
Accel/Decel]
0/1
0
The Accel/Decel time
is the time that takes
to reach the F21 –
[Max frequency] from
0 Hz.
0
X
1
The Accel/Decel time
is the time that takes
to reach a target
frequency from the
run frequency.
H71
[Accel/Decel
time scale]
0/2
0
Settable unit: 0.01
second.
1
O
1
Settable unit: 0.1
second.
2
Settable unit: 1
second.
H72
[Power on
display]
0/13
This parameter
selects the parameter to
be displayed on the
keypad when the input
power is first applied.
0
O
0 Frequency command
1 Accel time
2 Decel time
3 Drive mode
4 Frequency mode
5 Multi-Step frequency 1