7. Function List
7-14
LED
display
Parameter
Name
Min/Max
Range
Description
Factory
defaults
Adjustable
during run
Page
6 Multi-Step frequency 2
7 Multi-Step frequency 3
8 Output current
9 Motor rpm
10 Inverter DC link voltage
11 User display select
12 Fault display
13
Direction of motor
rotation select
H73
[Monitoring
item select]
0/2
One of the following
can be monitored via vOL
- [User display select].
0
O
0 Output voltage [V]
1 Output power [kW]
2 Torque [kgf
⋅
m]
H74
[Gain for
Motor rpm
display]
1/1000
[%]
This parameter is
used to change the
motor speed display to
rotating speed (r/min) or
mechanical speed
(m/mi).
100
O
H79
[Software
version]
0/10.0
This parameter
displays the inverter
software version.
X.X
X
H81
[2
nd
motor
Accel time]
0/6000
[sec]
This parameter is
active when the
selected terminal is ON
after I20-I24 is set to 12
{2
nd
motor select}.
5.0
O
H82
[2
nd
motor
Decel time]
10.0
O
H83
[2
nd
motor
base
frequency]
30/400
[Hz]
60.0
X
H84
[2
nd
motor
V/F pattern]
0/2
0
X
H85
[2
nd
motor
forward
torque
boost]
0/15 [%]
5
X
H86
[2
nd
motor
reverse
torque
boost]
-
5
X
100
74
31
120
H
H
f
RPM
×
×
=
Summary of Contents for 004iC5-1
Page 8: ......
Page 22: ...3 Wiring 3 6 ...
Page 38: ...5 Programming Keypad 5 14 ...
Page 42: ...6 Basic Operation 6 4 ...
Page 64: ...7 Function List 7 22 ...
Page 74: ...9 Specifications 9 4 ...