9. Specifications
9-2
Output
Multi-function
open collector
terminal
Operating status
and Fault output
(N.O., N.C.)
Below DV 24V 50mA
Multi-function
relay terminal
(N.O., N.C.) Below
AC250V 0.3A, Below DC 30V 1A
Analog output
0 ~ 10 Vdc : Frequency, Current, Voltage, DC link
voltage selectable
Protective functions
Inverter
Trip
Over-voltage, Under-voltage, Over-current, Ground fault current
detection, Over-temperature of inverter and motor, Output phase
open, Overload, Communication error, Loss of frequency command,
H/W fault
Alarm
Conditions
Stall prevention, Overload
Momentary
power loss
Less than 15 msec : Continuous operation
More than 15 msec : Auto Restart enable
Environment
Cooling
method
Forced air cooling
Degree of
protection
Open, Pollution degree 2
Ambient
temperature
-10
°
C ~ +50
°
C
Storage
temperature
-20
°
C ~ +65
°
C
Relative
humidity
Less than 90% (no condensation)
Altitude,
Vibration
1,000m above sea level, Max. 5.9m/sec
2
(0.6G)
Application
site
Protected from corrosive gas, combustible gas, oil mist or dust
Summary of Contents for 004iC5-1
Page 8: ......
Page 22: ...3 Wiring 3 6 ...
Page 38: ...5 Programming Keypad 5 14 ...
Page 42: ...6 Basic Operation 6 4 ...
Page 64: ...7 Function List 7 22 ...
Page 74: ...9 Specifications 9 4 ...