Code and
Features
Description
Ad.17 Dc-Brake
Freq
Set the frequency to start DC braking. When the frequency is
reached, the inverter starts deceleration.
If the dwell frequency is set lower than the DC braking frequency,
dwell operation will not work and DC braking will start instead.
•
Note that the motor can overheat or be damaged if an excessive amount of DC braking
is applied to the motor, or DC braking time is set too long.
•
The motor can be overheated or damaged. The maximum value of DC braking is
limited to the rated current of the inverter.
4.15.3 Free Run Stop
When the Operation command is off, the inverter output turns off, and the load stops
due to residual inertia.
Group Code
Name
Setting
Setting Range
Unit
Ad
08
Stop Mode
2
Free-
Run
0
–4
-
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...