7.5 Compatible Common Area Parameter
The following are common area parameters compatible with iS5, iP5A, iV5, and iG5A.
Comm.
Address
Parameter
Scale Unit R/W
Assigned Content by Bit
0h0000
Inverter model
-
-
R
16: G100
0h0001
Inverter capacity
-
-
R
0: 0.75kW, 1: 1.5kW, 2: 2.2kW,
4: 5.5kW, 5: 7.5kW,
6: 11kW, 7: 15kW, 8: 18.5kW,
9: 22kW
256 : 0.4kW, 259: 4.0kW
0h0002
Inverter input voltage
-
-
R
0: 220 V level, 1: 440 V level
0h0003
Version
-
-
R
(E.g.) 0h0100: Version 1.00
(E.g.) 0h0101: Version 1.01
0h0004
Reserved
-
-
R/W -
0h0005
Target frequency
0.01
Hz
R/W -
0h0006
Operation command
(option)
-
-
R
B15
Reserved
B14
0: Keypad Freq
1: Keypad Torq
2-16 Terminal block
multi-step speed
17: Up, 18: Down
19: STEADY
22: V1, 24: V0, 25: I2
26: Reserved
27: Built-in 485
28: Communication
option
30: JOG, 31: PID
B13
B12
B11
B10
B9
B8
0: Keypad
1: Fx/Rx-1
2: Fx/Rx-2
3: Built-in 485
4: Communication
option
B7
B6
R/W
B5
Reserved
B4
Emergency stop
B3
W: Trip initialization
(0
1)
R: Trip status
B2
Reverse operation (R)
B1
Forward operation (F)
B0
Stop (S)
0h0007
Acceleration time
0.1
sec
R/W -
0h0008
Deceleration time
0.1
sec
R/W -
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...