Code
Comm.
Address
Name
Setting Range
Initial
Value
Property
*
V/
F
S
L
Ref.
bA-83
Multi-step
deceleration
time 7
0.0
–600.0 (s)
20.0
O
O O
8.4 Expanded Function G
roup (PAR→Ad)
In the following table, data shaded in grey will be displayed when the related code has
been selected.
SL
: Sensorless vector control (dr.09), Property: Write-enabled during operation
Code
Comm.
Address
Name
Setting
Range
Initial
Value
Property* V/F SL Ref.
Ad-00
-
Jump Code
1
–99
24
O
O O
Ad-01
0h1301
Acceleration
pattern
0 Linear
0: Linear
X
O O
Ad-02
0h1302
Deceleration
pattern
1 S-curve
X
O O
Ad-03
9
0h1303
S-curve
acceleration
start point
gradient
1
–100 (%)
40
X
O O
Ad-04
0h1304
S-curve
acceleration
end point
gradient
1
–100 (%)
40
X
O O
Ad-05
10
0h1305
S-curve
deceleration
start point
gradient
1
–100 (%)
40
X
O O
Ad-06
0h1306
S-curve
deceleration
end point
gradient
1
–100 (%)
40
X
O O
Ad-07
0h1307 Start Mode
0 Acc
0: Acc
X
O O
1 Dc-Start
Ad-08
0h1308 Stop Mode
0 Dec
0: Dec
X
O O
1 Dc-Brake
9
10
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...