Installation
1
Remove the RJ45 terminal cover on the inverter I/O cover. Connect the remote
keypad cable to the I/O RJ45 connector.
2
Connect the other end of the connector of the remote keypad cable to the remote
keypad.
Enable
1
Once connected to the remote keypad, the key of the inverter keypad and the
button input of the jog controller are ignored. The input is replaced by the key and
volume input from the remote keypad.
•
Within 2 seconds of detaching the remote keypad, the input for the key and
volume is reset to the inverter keypad. (If the frequency setting is set to volume
input, the command frequency will instantly switch between the inverter keypad
volume and the remote keypad volume when attaching and detaching. Take
care so that the motor does not switch to the wrong frequency.)
•
If communication is not linked between the inverter and the remote keypad,
"E.vEr" is displayed on the 7-Seg of the remote keypad.
2
Set the dr 91 parameter to 4 in a state of connecting the remote keypad to copy
the parameter settings saved in the inverter to the remote keypad.
•
“r-UL” is displayed on the inverter I/O 7-Seg keypad while upload is in progress.
“d” is displayed on the 7-Seg keypad of the remote keypad. After saving, the
message disappears and the default screen is displayed.
•
If there is an error, such as poor communication while the upload is in progress,
a warning message saying "Fail" is displayed for 3 seconds, and the action of
saving the parameters into the remote keypad fails.
3
After connecting the remote keypad where the parameter settings are copied to
the inverter product of same model, set the dr 91 parameter to 5, and copy the
parameter settings saved in the remote keypad to the inverter.
•
While saving, a message saying “W-dL” is displayed on the inverter I/O 7-Seg.
"U" is displayed on the 7-Seg of the remote keypad. After saving, the message
disappears and the default screen is displayed. If parameter data is not saved
in the remote keypad, you cannot set the dr 91 parameter to 5.
•
If there is an error such, as poor communication with the remote keypad, a
warning message saying "Fail" is displayed for 3 seconds, and the action of
saving the parameters into the inverter fails.
•
If the parameter code version or the inverter model is different (copying
parameters between 200V
⇄
400V products), the WErr warning is displayed for
5 seconds, and the action of saving parameters into the inverter fails.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...